1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
If the room temperature is 6.0°C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
If the room temperature is 1.0°C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
Rotation number range of compressor
Unit: rps
Model name Minimum rotation number Maximum rotation number
ASUG09LZBS
ASUG12LZBS
ASUG15LZBS
8 130
Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
A zone
B zone
C zone
Outdoor
temperature rises
Outdoor
temperature drops
57.2°F
(14°C)
66.2°F
(19°C)
53.6°F
(12°C)
62.6°F
(17°C)
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
ASUG09LZBS
ASUG12LZBS
A zone 130 130 58 46
B zone 130 130 58 46
C zone 130 130 58 46
ASUG15LZBS
A zone 130 130 54 42
B zone 130 130 54 42
C zone 130 130 54 42
1-2. Heating operation - (04-3) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS