1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
14.0°F
(-10°C)
32.0°F
(0°C)
50.0°F
(10°C)
66.2°F
(19°C)
100.4°F
(38°C)
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
rotation number
AOUG09LZAS1
AOUG12LZAS1
A zone 37
B zone 37
C zone 37
D zone 28
E zone 1
F zone 22
AOUG15LZAS1
A zone 33
B zone 33
C zone 33
D zone 25
E zone 10
F zone 20
1-5. Limitation of compressor rotation number by outdoor temperature - (04-5) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS