8-3. Current release control
The rotation number of compressor is controlled so that the outdoor unit input current does not ex-
ceeds current limit value set according to the outdoor temperature.
The rotation number of compressor returns according to the operation mode, when the current be-
comes lower than the release value.
¢ Models: AOUH09LMAH1 and AOUH12LMBH1
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
122.0°F (50°C) ≤ Ta 4.0 A 3.5 A
114.8°F (46°C) ≤ Ta < 122.0°F
(50°C)
4.0 A 3.5 A
104.0°F (40°C) ≤ Ta < 114.8°F
(46°C)
5.0 A 4.5 A
53.6°F (12°C) ≤ Ta < 104.0°F
(40°C)
6.0 A 5.5 A
35.6°F (2°C) ≤ Ta < 53.6°F
(12°C)
6.0 A 5.5 A
Ta < 35.6°F (2°C) 6.0 A 5.5 A
Heating
62.6°F (17°C) ≤ Ta 5.5 A 5.0 A
53.6°F (12°C) ≤ Ta < 62.6°F
(17°C)
7.0 A 6.5 A
41.0°F (5°C) ≤ Ta < 53.6°F
(12°C)
7.5 A 7.0 A
Ta < 41.0°F (5°C) 8.5 A 8.0 A
8-4. Cooling pressure over-rise protection
When the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition 149.0°F (65°C)
8-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition 226.4°F (108°C)
Release condition
176.0°F (80°C)
(3 minutes after compressor stop)
8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart