1-2. Outdoor unit
Type Inverter heat pump
Model name AOUH09LMAH1 AOUH12LMBH1
Power supply 208/230 V~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Starting current A 3.9 4.8
Fan
Airflow rate
Cooling
CFM (m
3
/h)
901 (1,530) 1,065 (1,810)
Heating 901 (1,530) 1,065 (1,810)
Type × Q'ty Propeller fan × 1
Motor output W 23
Sound pressure level *
Cooling
dB (A)
46 49
Heating 48 50
Heat exchanger type
Dimensions
(H × W × D)
in (mm)
Main1: 19-13/16 × 34-11/16 × 11/16 (504 × 881 × 18.19)
Main2: 19-13/16 × 33-1/2 × 11/16 (504 × 851 × 18.19)
Fin pitch FPI 20
Rows × Stages
Main1: 1 × 24
Main2: 1 × 24
Pipe type Copper
Fin type
Type (Material) Aluminum
Surface treatment PC fin
Compressor
Type DC rotary
Motor output W 900
Refrigerant
Type R410A
Charge
lb oz 2 lb 3 oz 2 lb 3 oz
g 1,000 1,000
Refrigerant oil
Type RB68A
Amount
in
3
(cm
3
)
20.7 (340)
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
in (mm)
21-5/16 × 31-7/16 × 11-7/16 (542 × 799 × 290)
Gross 23-11/16 × 37 × 14-3/4 (602 × 940 × 375)
Weight
Net
lb (kg)
73 (33)
Gross 79 (36)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52)
Method Flare
Pre-charge length
ft (m)
49 (15)
Max. length 66 (20)
Max. height difference 49 (15)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46)
Heating -15 to 75 (-26 to 24)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80°FDB (26.67°CDB)/67°FWB (19.44°CWB), and outdoor temperature of 95°FDB (35°CDB)/75°FWB (23.9°CWB).
Heating: Indoor temperature of 70°FDB (21.11°CDB)/60°FWB (15.56°CWB), and outdoor temperature of 47°FDB (8.33°CDB)/43°FWB (6.11°CWB).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-2. Outdoor unit
- (01-3) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION

Table of Contents

Other manuals for Fujitsu ASUH09LMAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH09LMAS and is the answer not in the manual?

Fujitsu ASUH09LMAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH09LMAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals