2-5. Wall mounted type (ASUH18-24LPAS)
Model name ASUH18LPAS ASUH24LPAS
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 18,000 24,000
Input power W 34 55
Running current A 0.32 0.46
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
530 (900) 642 (1,090)
MED 471 (800) 530 (900)
LOW 377 (640) 471 (800)
QUIET 241 (410) 306 (520)
Heating
HIGH 506 (860) 594 (1,010)
MED 406 (690) 506 (860)
LOW 330 (560) 377 (640)
QUIET 247 (420) 306 (520)
Type × Qty Crossflow fan × 1
Motor output W 59
Sound pressure level*1
Cooling
HIGH
dB (A)
44 49
MED 42 44
LOW 37 42
QUIET 26 31
Heating
HIGH 43 47
MED 39 43
LOW 34 37
QUIET 28 32
Heat exchanger type
Dimensions (H × W × D) in (mm)
Main1: 8-1/4 × 31-5/16 × 1-1/16 (210 × 796 × 26.6)
Main2: 4-15/16 × 31-5/16 × 1-1/16 (126 × 796 × 26.6)
Sub1: 3-5/16 × 31-5/16 × 1/2 (84 × 796 × 13.3)
Fin pitch FPI
Man1: 21
Main2: 21
Sub1: 18
Rows × Stages
Main1: 2 × 10
Main2: 2 × 6
Sub1: 1 × 4
Pipe type Copper
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
in (mm)
11 × 38-9/16 × 9-7/16 (280 × 980 × 240)
Gross 12-11/16 × 42-7/16 × 13-5/8 (322 × 1,078 × 346)
Weight
Net
lb (kg)
29 (13)
Gross 37 (17)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø1/2 (Ø12.7)
Ø5/8 (Ø15.88)*
2
Method Flare
Drain hose
Material PP+HDPE
Tip diameter in (mm) Ø17/32 (Ø13.8) (I.D.), Ø5/8 to 21/32 (Ø15.8 to 16.7) (O.D.)
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 86 or less (30 or less)
Remote controller type
Wireless (Wired, Mobile app*3 [FGLair
â„¢
] [option])
NOTES:
• The protective function might work when using it outside the operation range.
• *1: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *2: Use the attached adapter to change the pipe size from Ø1/2 in (Ø12.7 mm) to Ø5/8 in (Ø15.88 mm).
• *3: Available on Google Play
â„¢
store or on App Store
®
. Optional WLAN Adapter is also required. For details, refer to the setting manual.
- 11 -
2-5. Wall mounted type (ASUH18-24LPAS) 2. Specifications
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type