Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Unit: in (mm)
Front View Side View Rear View
2-15/16 (75)
3/4 (19)
Hole: 3/8 × 3/16 (9 × 4.5)
7/8 (23.0)
1-3/16
(30.0)
1-3/16
(30.0)
Hole: 4/16 × 3/16 (6 × 4.5)
Hole: 1/2 × 3/16 (12.5 × 4.5)
4-3/4 (120)
9/16 (14.7)
3/4
(18.8)
1-9/16 (39.8) 1-3/4 (44.7)
Size (H × W × D) in (mm) 4-3/4 × 2-15/16 × 3/4 (120 × 75 × 19)
Weight oz (g) 4.2 (120)
Cable length (accessory) ft (m) 33 (10)
Power V 12
 Wiring specifications
Use Cable size Wire type Remarks
Remote controller cable
22 to 16 AWG (0.33 to
1.25 mm
2
)
Non-polar 2-core,
Twisted pair
Use sheathed PVC cable.
¢
Installation
Connect the end of remote controller cable directly to the exclusive terminal block.
Terminal block
Functional earthing
(If necessary)
Remote controller cable
(Non-polar)
Indoor unit PCB
NOTES:
• Layout of terminal block and PCB is varies depending on the type of indoor unit.
• Operation may fail if it is connected to the outdoor unit or the terminal block for power sup-
ply.
- 183 -
15-8. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) 15. Remote controller