13) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable ♦*
01 Enable
02 Remote controller ♦
*: For RLF1 series wall mounted and floor type indoor unit only.
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTE:
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter. To confirm if the remote con-
troller has this setting, refer to the operating manual of each remote controller.
14) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
• For compact cassette type and LPAS series wall mounted type indoor unit
Function number Setting value Setting description Factory setting
60
00 Operation status ♦
01—04 Cooling thermostat On
05 Heating operation
06 Operation/Stop
07—08 Cooling thermostat On
09 Error status
10 Indoor unit fan operation status
11 External heater
• For slim duct type indoor unit
Function number Setting value Setting description Factory setting
60
00 Operation status ♦
01—04 Cooling thermostat On
05 Heating operation
06 Operation/Stop
07—08 Cooling thermostat On
09 Error status
10 Fresh air control
11 External heater
- 212 -
16-6. Function details 16. Function settings
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type