3-7. Too warm
Forecast of cause
House insulation setting has not been changed.
Temperature sensing location has not been changed.
Installation location of the wired remote.
Function settings have not been changed.
Check point 1. Check insulation level of structure of house
Is insulation level greater than R-13?
→ If no, go to "Check Point 4".
Check point 2. Check function setting
If insulation level is greater than R-13 set function 95 to 01.
NOTE: For details of function setting number 95, refer to "Function settings " in Chapter 5. FIELD
WORKING on page 05-1.
Check Point 3. Check effects of function setting change
Is the space still too warm in relation to setpoint?
Check Point 4. Verify room temperature sensing location
Do you want room temperature sensed at the wired remote controller (Wired remote sensor) or by
they build in sensor inside the unit (Indoor unit sensor)?
→ If indoor unit sensor, go to "Check Point 5".
→ If wired remote sensor, go to "Check point 8".
Check Point 5. Check the remote controller display
Is the "Thermo Sensor Icon" displayed on the screen?
→ If no, go to "Check point 7".
3-7. Too warm - (03-41) - 3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ASUH24LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH24LPAS and is the answer not in the manual?

Fujitsu ASUH24LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH24LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals