When function setting is “Operation/Stop” mode 2
In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-03 1
External input and
output PCB
CN313
Off → On Operation
On → Off
Stop (R.C.
disabled)
On
CN313
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
On OnOff
In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input Input signal Command
46-03 1
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
(R.C. disabled)
Off
On
NOTE: When “Operation/Stop” mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
- 23 -
8-4. Details of function
8. External input and output
WALL MOUNTED
ASUH30-36LPAS
WALL MOUNTED
ASUH30-36LPAS

Table of Contents

Other manuals for Fujitsu ASUH30LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH30LPAS and is the answer not in the manual?

Fujitsu ASUH30LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH30LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals