Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA24/30LCC
[Condition]
Ambient
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYA24LCC ASYA30LCC
outdoor unit overall current with the current clamp meter at Power Cable.
length
08-03
Under Construction
Under Construction
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
0 2 4 6 8 10 12 14
Outdoor ambient temperature[ C]
High-pressure of outdoor unit[MPa]
23 C
20 C
15 C
[50Hz-230V]
Indoor ambient
temperature[ C]
12.0
12.5
13.0
13.5
14.0
14.5
15.0
15.5
16.0
0 2 4 6 8 10 12 14
Outdoor ambient temperature[ C]
Outdoor total electric current[A]
23 C
20 C
15 C
[50Hz-230V]
Indoor ambient
temperature[ C]