JP (Jumper) Setting
[Indoor Unit]
ASYA07/09/12LCC
ASYB09/12LDC
ASYA14/18LCC
- Remote control custom code
When multiple number of indoor units are installed in the same room, erroneous receipt of the signal can
be avoided by setting up the remote control custom code separately.
To set up the remote control custom code, always set up the same code on both indoor unit PCB and
remote control PCB.
(When the indoor unit PCB is changed to Code B, it can not receive the signal unless remote control PCB
is also changed to Code B.)
Indoor Unit Remote Control
JM1(JP)
J4 (JP)
Code A (Default)
Code B
- Auto Restart
It is possible to disengage Auto Restart function if it is not needed.
Indoor Unit
JM2 (JP)
With Auto Restart function
(Default)
Without Auto Restart
function
[Outdoor Unit]
AOYR07/09/12LCC
JP
JM500 JM103 JM102 JM101
Normal Preheat
07/09LCC
Higher Preheat
Normal Preheat
12LCC
Higher Preheat
AOYS09/12LDC
AOYR14/18LCC
- it is possible to select the higher or standard level of preheating function.
- When it is set up at the higher level of preheat, the magnetic noise of the compressor becomes higher.
08-01
JP
JM500 JM103 JM102 JM101
Normal Preheat
09LDC
Higher Preheat
Normal Preheat
12LDC
Higher Preheat
JP
JM500 JM103 JM102 JM101
Normal Preheat
14LCC
Higher Preheat
Normal Preheat
18LCC
Higher Preheat