Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA14LCC, ASYA18LCC
[Condition]
Ambient
temperature
Indoor 15 - 23degC, Outdoor 2 - 12degC
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
ASYA14LCC ASYA18LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
ASYA14LCC ASYA18LCC
Measure the high pressure with the pressure meter at the service valve. Measure the
outdoor unit overall current with the current clamp meter at Power Cable.
6.5
7
7.5
8
8.5
9
051015
Outdoor ambient temperature [degC]
Outdoor Total Electric Current (A)
Indoor inlet temp :15 C
Indoor inlet temp :20 C
Indoor inlet temp :23 C
length
08-07
2.50
2.70
2.90
3.10
3.30
3.50
3.70
3.90
0 2 4 6 8 101214
Outdoor ambient temparature [degC]
High-pressure of outdoor unit [MPa]
Indoor inlet temp
15degC
Indoor inlet temp
20degC
Indoor inlet temp
23degC
6.00
6.20
6.40
6.60
6.80
7.00
7.20
7.40
7.60
7.80
8.00
02468101214
Outdoor ambient temparature [degC]
Outdoor total electric current [A]
Indoor inlet temp
15degC
Indoor inlet temp
20degC
Indoor inlet temp
23degC
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4
02468101214
Outdoor ambient temparature [degC]
High-pressure of outdoor unit
[MPa]
15degC
20degC Indoor ambient temp. )
23degC