2-16. E: 94. Trip detection (Outdoor unit)
Indicator Indoor unit
Operation indicator 9 time flash
Timer indicator 4 time flash
Economy indicator Continuous flash
Error code E: 94
Detective actuator Outdoor unit
Main PCB Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE: The number of generations is reset when the
compressor starts up.
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check point 2. Replace main PCB
If Check point 1 do not improve the symptom, change main PCB.
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
End
2-16. E: 94. Trip detection (Outdoor unit) - (03-20) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ASYG09KHCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG09KHCA and is the answer not in the manual?

Fujitsu ASYG09KHCA Specifications

General IconGeneral
BrandFujitsu
ModelASYG09KHCA
CategoryAir Conditioner
LanguageEnglish

Related product manuals