8. COMPRESSOR CONTROL
01-08
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 11.
Cooling / Dry Heating
Minimum Maximum Minimum Maximum
AO*G07/09LLCC
AO*G12LLCC
18rps
16rps
18rps
16rps
120rps
109rps
64rps
87rps
AO*G07/09LLCC
56rps 67rps 75rps
(Table 11 : Compressor frequency range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.9.
(Fig.9 : Compressor control at start-up)
Time
Time Time Time
Time
(Frequency)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time Time Time
Time
(Time)
78rps 78rps
Frequency
Time
6
Frequency
Time
6
78rps
AO*G12LLCC
51rps 67rps 79rps 88rps 98rps 108rps
AO*G07/09LLCC
80sec 140sec 200sec 380sec 440sec 440sec
AO*G12LLCC
AO*G07/09LLCC
AO*G12LLCC
AO*G07/09LLCC
AO*G12LLCC
60sec 100sec 140sec 200sec 350sec 410sec
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
Under Over Under Over Under Over
35rps 23rps
44rps 28rps
34rps 22rps
44rps 28rps
30rps
-------
(Table12 : Limitation of Compressor Frequency)
10°C 14°C 40°C
Under Over Under Over Under Over Under Over
30rps
-------
- 3°C 7°C 14°C 40°C
[ Cooling/ Dry ]
[ Heating ]
30rps
30rps

Other manuals for Fujitsu ASYG09LLCC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG09LLCC and is the answer not in the manual?

Fujitsu ASYG09LLCC Specifications

General IconGeneral
BrandFujitsu
ModelASYG09LLCC
CategoryAir Conditioner
LanguageEnglish

Related product manuals