EasyManuals Logo

Fujitsu ASYG12LLCE Service Instruction

Fujitsu ASYG12LLCE
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
6. OUTDOOR FAN CONTROL
01-06
( Table 9 : Outdoor fan speed )
*
The outdoor fan speed mentioned above depends on the compressor frequency.
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
as table10 without relating to the compressor frequency.
( Table10 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor DC Motor
Following table shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table 8 : Type of Motor )
Model 07/09/12
900rpm
Cooling Heating
Y
Z
Zone
Refer to Fig.8
(rpm)
F
G
Y
Z
F
G
Dry
260/ 200
360/ 150
380/ 260
730/ 650/ 470
860/ 780/ 720/ 680/ 470
860/ 470/ 380
900/ 650/ 470 730/ 470
900/ 760/ 720/ 680/ 470 760/ 470
730/ 470/ 360
210/ 150
( Fig.8 : Outside air temperature zone selection )
21°C
10°C
Outside air
temperature rises
Outside air
temperature drops
Z zone
Y zone
F zone
G zone
12°C
C
19°C
C
Model 07/ 09
Model 12
Model 07/09/12

Other manuals for Fujitsu ASYG12LLCE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG12LLCE and is the answer not in the manual?

Fujitsu ASYG12LLCE Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Inverter technologyYes
Air conditioner functionsCooling, Dehumidifying, Heating
Cooling capacity in watts (nominal)- W
Airflow720 m³/h
Outdoor unit noise level- dB
AC input voltage230 V
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit typeWall-mountable
Indoor unit depth206 mm
Indoor unit width820 mm
Indoor unit height262 mm
Indoor unit weight7000 g
Indoor unit noise level (high speed)43 dB