EasyManua.ls Logo

Fujitsu AUXG07-22KVLA - Page 175

Fujitsu AUXG07-22KVLA
523 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Wall mounted
ASYG07KMCC
250 V, 3.15 A
Activate: 170
+25
-30
°C
Fan motor stop
Reset: 145
+25
-30
°C
Fan motor restart
ASYG09KMCC
ASYG12KMCC
ASYG14KMCC
ASYG07KMCE
Activate: 170
+25
-30
°C
Fan motor stop
Reset: 145
+25
-30
°C
Fan motor restart
ASYG09KMCE
ASYG12KMCE
ASYG14KMCE
ASYG07KETA
ASYG07KETA-B
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
ASYG09KETA
ASYG09KETA-B
ASYG12KETA
ASYG12KETA-B
ASYG14KETA
ASYG14KETA-B
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG07KETE
ASYG07KETE-B
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
ASYG09KETE
ASYG09KETE-B
ASYG12KETE
ASYG12KETE-B
ASYG14KETE
ASYG14KETE-B
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
Ceiling
ABYG18KRTA 250 V, 3.15 A Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
108 °C Off
ABYG22KRTA 250V, 5.0 A
Floor
AGYG09KVCA
250V, 5.0 A
Activate: 150 ±15 °C
Fan motor stop
Reset: 120 ±15 °C
Fan motor restart
110 °C Off
AGYG12KVCA
AGYG14KVCA
*: Printed Circuit Board
- 167 -
10. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Related product manuals