EasyManua.ls Logo

Fujitsu AUXG07-22KVLA - Safety Devices

Fujitsu AUXG07-22KVLA
523 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. Safety devices
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Compact
cassette
AUXG07KVLA
250 V, 5 A
Activate: 100 ±15 °C
Fan motor stop
Reset: 95 ±10 °C
Fan motor restart
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
AUXG18KVLA
AUXG22KVLA
Mini duct
ARXG07KSLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
ARXG18KSLAP
Slim duct
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
Medium static
pressure duct
ARXG22KMLB
Wall mounted
ASYG07KGTB
250 V, 3.15 A
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
ASYG09KGTB
ASYG12KGTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTB
ASYG07KGTE Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
ASYG09KGTE
ASYG12KGTE Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG14KGTE
ASYG18KMTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG22KMTB
ASYG24KMTB
ASYG18KMTE Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASYG22KMTE
ASYG24KMTE
ASYG07KMTB Activate: More than 95 °C
Fan motor speed down
Reset: 95 °C or less
Fan motor speed recover
ASYG09KMTB
ASYG12KMTB
ASYG14KMTB
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
- 166 -
10. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents