Dimensions and other specifications on the wired remote controller are as follows.
20.4120
120
[Unit:mm]
Model name UTY-RNRYZ*
Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel
Dimensions (H × W × D) mm 120 × 120 × 20.4
Weight g 220
Input voltage V DC 12
Power consumption W Max. 0.3
Usage temperature range °C 0 to 40
Usage humidity range % 20 to 90 (no condensation)
Storage temperature range °C -10 to 60
Storage humidity range % 20 to 90 (no condensation)
Wiring specifications
Use Cable size Wire type Remarks
Remote controller cable
0.33 to 1.25 mm
2
Non-polar 2-core,
Twisted pair
Use sheathed PVC cable.
¢
Installation
Connect the end of remote controller cable directly to the exclusive terminal block.
Terminal block
Indoor unit PCB
Functional earthing
(If necessary)
Remote controller cable
(Non-polar)
Y1 Y2
TO REMOTE CONTROL UNIT Ex IN
Y3 1 2
NOTES:
Layout of terminal block and PCB is varies depending on the type of indoor unit.
Operation may fail if it is connected to the outdoor unit or the terminal block for power sup-
ply.
- 259 -
13-11. Wired remote controller (UTY-RNRYZ*: Optional part) 13. Remote controller
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07-22KVLA and is the answer not in the manual?

Fujitsu AUXG07-22KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07-22KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals