1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOYG09KATA
A zone 50 rps
B zone 50 rps
C zone 40 rps
D zone 40 rps
E zone 16 rps
F zone 21 rps
AOYG12KATA
A zone 42 rps
B zone 42 rps
C zone 33 rps
D zone 28 rps
E zone 16 rps
F zone 21 rps
AOYG14KATA
A zone 40 rps
B zone 40 rps
C zone 28 rps
D zone 1 rps
E zone 1 rps
F zone 20 rps
AOYG18KATA
A zone 36 rps
B zone 36 rps
C zone 28 rps
D zone 1 rps
E zone 1 rps
F zone 20 rps
AOYG22KATA
A zone 30 rps
B zone 30 rps
C zone 22 rps
D zone 16 rps
E zone 13 rps
F zone 25 rps
1-5. Compressor frequency limitation by outdoor temperature - (04-7) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?

Fujitsu AUXG14KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG14KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals