7-7. External electrical heater control
The external electrical heater is operated as below.
When the room
temperature rises
When the room
temperature drops
Ts: Setting temperature
Heater : Off
Heater : On
Heater : Off
Ts -10°C
Ts -1°C
Ts -3°C
Ts -12°C
NOTES:
When the compressor stop, external electric heater is off.
It operates only in heating mode and when the indoor fan operates. (However, S-LOW is exclud-
ed.)
7-8. Electronic expansion valve control
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the table below.
Operation mode Pulse range
Cooling/dry mode
Between 52 and 480 pulses
Heating mode
NOTE: At the time of supplying the power to the outdoor unit, the initialization of the electronic ex-
pansion valve is operated (528 pulses are input to the closing direction).
7-7. External electrical heater control - (04-30) - 7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?

Fujitsu AUXG14KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG14KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals