EasyManuals Logo

Fujitsu AUXG14KVLA Service Instruction

Fujitsu AUXG14KVLA
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
Trouble shooting 6
INDOOR UNIT Error Method:
Detective Actuators: Detective details:
1. The outdoor unit receives the serial signal of applied refrigerant
information from Indoor unit. When the refrigerant is R410a.
2. When the outdoor unit type is multi.
Forecast of Cause:
OK
Combination error
Indoor unit
1. The selection of indoor units is incorrect
Check Point 1 : Check the type of indoor unit
Check the type of the connected indoor unit.
>> If abnormal condition is found, correct it.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB of Outdoor unit.
Indicate or Display:
Error code : 23
02-07
Outdoor unit : No indication

Other manuals for Fujitsu AUXG14KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG14KVLA and is the answer not in the manual?