Models: AOHG45KRTA and AOHG54KRTA
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step Cooling or dry Heating
13 990
12 920
11 860
10 800 990
9 740 900
8 650 820
7 600 740
6 530 650
5 490 540
4 400 460
3 330 380
2 270 290
1 200 200
S-HIGH 990
When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 990 rpm
3-2. Outdoor fan control - (04-19) - 3. Fan control