8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOHG36KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 3.5 A 3.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
42°C ≤ Ta < 50°C 6.0 A 5.5 A
2°C ≤ Ta < 42°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
Heating
20°C ≤ Ta 5.5 A 5.0 A
16°C ≤ Ta < 20°C 6.0 A 5.5 A
12°C ≤ Ta < 16°C 7.0 A 6.5 A
2°C ≤ Ta < 12°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
¢ Models: AOHG45KRTA and AOHG54KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 4.5 A 4.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
46°C ≤ Ta < 50°C 6.5 A 6.0 A
42°C ≤ Ta < 46°C 7.5 A 7.0 A
2°C ≤ Ta < 42°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
Heating
20°C ≤ Ta 6.5 A 6.0 A
16°C ≤ Ta < 20°C 7.0 A 6.5 A
12°C ≤ Ta < 16°C 8.0 A 7.5 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
8-3. Current release control - (04-35) - 8. Various protections