6-5. Model: AOHG36KBTB
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.902 0.882 0.862
20 0.938 0.917 0.897 0.876
10 0.973 0.953 0.933 0.912 0.891
7.5 0.988 0.977 0.957 0.936 0.916 0.895
5 0.992 0.992 0.981 0.961 0.940 0.919 0.898
0 1.000 1.000 0.989 0.968 0.947 0.926 0.905
Indoor unit is lower than
outdoor unit *2
-5 1.000 1.000 0.989 0.968 0.947 0.926 0.905
-7.5 1.000 0.989 0.968 0.947 0.926 0.905
-10 0.989 0.968 0.947 0.926 0.905
-20 0.968 0.947 0.926 0.905
-30 0.947 0.926 0.905
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.978 0.968 0.958
20 0.988 0.978 0.968 0.958
10 0.998 0.988 0.978 0.968 0.958
7.5 1.000 0.998 0.988 0.978 0.968 0.958
5 1.000 1.000 0.998 0.988 0.978 0.968 0.958
0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973 0.963 0.953
-7.5 0.993 0.991 0.981 0.971 0.961 0.951
-10 0.988 0.978 0.968 0.958 0.948
-20 0.968 0.958 0.949 0.939
-30 0.949 0.939 0.929
- 86 -
6-5. Model: AOHG36KBTB
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18-45KBTB
OUTDOOR UNIT
AOHG18-45KBTB

Table of Contents