4.4.1. Wired or Simple remote controller wiring method
The optional parts wiring method for “Wired remote controller” or “Simple remote
controller” is as follows.
2
1
3
4
Cable with core
Cable (Place along)
to remote controller
Hook (L) + Cable (Back)
Communication kit
Communication kit
Hook (L)
+
Cable (Back)
Hook (R)
+
Cable (Front)
Core (large)
Close
Cable tie
(Fixed diagonally)
Push mount cable tie
Connection
number (P 190)
Control cover
Vinyl tape
Install the control cover.
4.4.2. External input and output
External input
Indoor unit functions such as Operation/Stop or Forced stop can be done by using
indoor unit terminals.
“Operation/Stop” mode or “Forced stop” mode can be selected with function setting of
indoor unit.
A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
The wire connection should be separate from the power cable line.
Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
PCB
Connector
(CN14/CN15)
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Operation behavior
Input signal type
Edge
ON
OFF
When function setting is “Operation/Stop” mode 1.
Input signal Command
OFF ON Operation
ON OFF Stop
When function setting is “Forced stop” mode.
Input signal Command
OFF ON Forced stop
ON OFF Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
When function setting is “Operation/Stop” mode 2.
Input signal Command
OFF ON Operation
ON OFF Stop (R.C. disabled)
NOTE: For details, refer to “ Combination of external input and output” in “5.1. Function
details”.
External output
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
Output voltage: Hi DC12V±2V, Lo 0V.
Permissible current: 50mA
Output select
When interlocking with external device
Connector
(CN20/CN21/
CN22/CN23)
PCB
Connected
device
Relay (Locally purchased)
or
When displaying “Operation/Stop”
Connector
(CN20/CN21/
CN22/CN23)
PCB
Connected device
Resistor
LED
Operation behavior
*If function setting “60” is set to “00”, refer to “5. FUNCTION SETTING”.
4.5. Side panel L and control cover installation
]
Install Side panel L and control cover by the reverse procedures as stated in “4.3. Side
panel L and control cover removal”.