Fujitsu KVC Series - 10 Refrigerant Leak Detection Function

Fujitsu KVC Series
15 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-14
Error display
Error code* Description
LED1
(orange)
LED2
(green)
LED3
(green)
(4)
(4)
44
Human sensor error
(5)
(4)
45
Refrigerant leakage sensor error
Sensor error, and harness
disconnection/connection failure
may have occurred.
(1)
(5)
51
Indoor unit fan motor error
(3)
(5)
53
Drain pump error
(4)
(5)
54
Electric air cleaner reverse VDD
error
(5)
(5)
55
Filter set error
(7)
(5)
57
Damper error
(8)
(5)
58
Intake grille error
(9)
(5)
59
Indoor unit fan motor 2 error
(Left side fan)
(10)
(5)
5A
Indoor unit fan motor 3 error
(Right side fan)
(15)
(5)
5U
Indoor unit error
(1)
(6)
61
Outdoor unit reverse/missing
phase and wiring error
(2)
(6)
62
Outdoor unit main PCB
model information error or
communication error
(3)
(6)
63
Inverter error
(4)
(6)
64
Active filter error, PFC circuit error
(5)
(6)
65
• Trip terminal L error
• IPM temp error
(8)
(6)
68
Outdoor unit rush current limiting
resister temp. rise error
(10)
(6)
6A
Display PCB microcomputers
communication error
(1)
(7)
71
Discharge temp. sensor error
(2)
(7)
72
Compressor temp. sensor error
(3)
(7)
73
Outdoor unit Heat Ex. liquid temp.
sensor error
(4)
(7)
74
Outdoor temp. sensor error
(5)
(7)
75
Suction Gas temp. sensor error
(6)
(7)
76
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
(7)
(7)
77
Heat sink temp. sensor error
(2)
(8)
82
• Sub-cool Heat Ex. gas inlet
temp. sensor error
• Sub-cool Heat Ex. gas outlet
temp. sensor error
(3)
(8)
83
Liquid pipe temp. sensor error
(4)
(8)
84
Current sensor error
(6)
(8)
86
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
(4)
(9)
94
Trip detection
(5)
(9)
95
Compressor rotor position
detection error (permanent stop)
(7)
(9)
97
Outdoor unit fan motor 1 error
Error display
Error code* Description
LED1
(orange)
LED2
(green)
LED3
(green)
(8)
(9)
98
Outdoor unit fan motor 2 error
(9)
(9)
99
4-way valve error
(10)
(9)
9A
Coil (expansion valve) error
(1)
(10)
A1
Discharge temp. error
(3)
(10)
A3
Compressor temp. error
(4)
(10)
A4
High pressure error
(5)
(10)
A5
Low pressure error
(8)
(10)
A8
Refrigerant leakage suspicion
(11)
(10)
AC
Heat sink temp error
(2)
(13)
J2
Branch boxes error
[Multi-split type]
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
Error code on the wired remote controller (option)
Check the error
1.
If an error occurs, an error icon appears on the “Monitor mode screen”.
Touch the [Status] on the “Monitor mode screen. The “Status” screen is dis-
played.
2.
Touch the [Error Information] on the “Status” screen. The “Error Information”
screen is displayed. (If there are no errors, the [Error Information] will not be
displayed.)
3.
2-digit numbers correspond to the error code in the table.
Touch the [Next page] (or [Previous page]) to switch to other connected indoor
units.
1. 2. 3.
Set Temp.
Mode
MenuStatus
Fan
Fri 10:00AM
Unoccupied
Status
Air Flow Direction
VT
Off
13
Off
HZ
Economy
Individual
Anti Freeze
Page 1/ 4
Monitor
Next
Page
Error
Information
02-01
14,15, 41, 44
Error Information
Page 1/ 5
Address
Error Code
Back
Next
Page
]1]1
10. REFRIGERANT LEAK DETECTION FUNCTION
System operation after refrigerant leak detection:
Indoor unit starts diffusion operation by high fan speed.
Due to safety reasons, a remote controller cannot stop this operation.
Indoor unit indicates Error code A8 (TIMER lamp [8], OPERATION lamp [10]).
[ ]: Number of flashing
Indoor unit makes a warning beep.
(The beep stops by pressing [START/STOP] of the remote controller or [MANUAL
AUTO] on the indoor unit.)
System stops the cooling/heating operation. Forced cooling operation is not available.
9378533080-04_IM.indb 149378533080-04_IM.indb 142022/2/14 15:13:152022/2/14 15:13:15