14
Description of sections
- Settings
pg. 1 Current limit per 1 phase - at one phase units may experience overloading when runs together with bivalent source;
this function cause that first stage of bivalent source will not be used for bivalent operation
Secondary circuit - define if the seconadry circuit control is used (external mixing valves)
Outdoor unit max power - enable to set outdoor unit maximal power (mainly used for noise reduction)
Only in the attenuation - outpdoor unit power limit is active only when attenuation is active
Bivalent operation - if the outdoor temperature is lower than this limit, for heating is used bivalent source only
Cooling water - output water temperature in cooling mode (keep temperature above dew point (ca. 18°C and more)
is necessary
pg. 2 Date / time - date and time settings
Webserver - name - webserver login name
Webserver - password - webserver login password
Saved data - heat pump operation saved data (access is possible only from PC)
Network settings - ethernet network connection settings
pg. 3 Service access - access only for service engeneer
pg. 1 Secondary source - enable use of secondary source (solid fuel boiler, solar panel, etc.)
Secondary source tank temp. - actual temperature in secondary source accumulation tank
Secondary source hysteresis - if the accumulation tank temperature is higher than temperature computed by
equithermal curve + hysteresis, the heat pump is stopped and secondary circuit starts. Thereby is heat
transferred from accumulation tank to object.
Pool - pool heating switch ON / OFF
Pool temperature - actual pool temperature
pg. 2 Required pool temperature - required pool temperature
Required pool hysteresis - pool heating hysteresis
Temp. of pool heating water - temperature of output water for pool heating
Pool heating time schedule - time schedule for pool heating (one time zone per day)