1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
Compressor frequency range
Model name Minimum frequency Maximum frequency
AUXG24KRLB 14 rps 101 rps
Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
AUXG24KRLB
A zone 101 74 62 46
B zone 101 74 62 46
C zone 85 68 56 46
D zone 74 56 46 27
E zone 74 56 46 27
F zone 74 56 46 27
1-1. Cooling operation - (04-1) - 1. Compressor frequency control