1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOYG24KATA
A zone 33 rps
B zone 33 rps
C zone 31 rps
D zone 19 rps
E zone 1 rps
F zone 20 rps
Heating mode
F zone
19°C
E zone
5°C
D zone
0°C
C zone
B zone
A zone
-15°C
-25°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOYG24KATA
A zone 31 rps
B zone 31 rps
C zone 21 rps
D zone 13 rps
E zone 1 rps
F zone 1 rps
1-5. Compressor frequency limitation by outdoor temperature - (04-4) - 1. Compressor frequency control