1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
Compressor frequency range
Unit: rps
Model name Minimum frequency Maximum frequency
AUXG24KRLB 14 130
Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
A zone
12°C
B zone
14°C
C zone
-10°C
-12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
AUXG24KRLB
A zone 130 101 85 81
B zone 130 101 85 81
C zone 130 101 85 81
1-2. Heating operation - (04-2) - 1. Compressor frequency control