Line Function Setting range or display Setting
increment
Basic setting
1610 Nominal setpoint Reduced setting (line 1612)…
to 65 °C
1
The backup electrical system is required to reach this level.
1612 Reduced setpoint 8 °C...
to Nominal setpoint (line 1610)
1
2056 Setpoint source heating 8... 35 °C
6711 Reset HP No, Yes
7141 Emergency operation Off, On
Off : The heat pump does not use the boiler connection when a fault occurs (error 370).
On : The heat pump uses the boiler connection when a fault occurs (error 370).
In the "On" position, the energy costs can be onerous if the error is not eliminated.
8410 Return temp HP 0... 140 °C
Setpoint (return) HP 0... 140 °C
8412 Flow temp HP 0... 140 °C
Setpoint (ow) HP 0... 140 °C
8413 Compressor modulation 0... 100%
8700 Outdside temperature -50... 50 °C
8701 Outside temp min
Reset ? (No, Yes)
-50... 50 °C
8702 Outside temp max
Reset ? (No, Yes)
-50... 50 °C
8740 Room temperature 1 0... 50 °C
Room setpoint 1 4... 35 °C
8743 Flow temperature 1 0... 140 °C
Flow temperature setpoint 1 0... 140 °C
8756 Flow temp cooling 1 0... 140 °C
Flow temp setpoint cooling 1 0... 140 °C
8830 DHW (domestic hot water) temperature 0... 140 °C
DHW temperature setpoint 5... 80 °C
Operation manual "1408 - EN" - 11 -