DIGITAL CONTROLLER FOR FREEZING SYSTEMS
WITH DEFROST SCHEDULING AND INTERNAL
DATALOGGER
4. INDICATIONS AND KEYS
6. OPERATIONS
6.1 Quick Access Menu Map
To access or navigate the quick access menu using the ;(short press) key while the controller is
displaying the temperature. For every touch, the next function in the list is displayed. To confirm, use the
/(short press) key.
1. DESCRIPTION
Designed to better safeguard frozen products. TC-900e Log is equipped with 3 relays (Comp,
Defrost & Fan), 2 temperature sensors, 2 digital inputs, real-time clock, data logger and light intensity
sensor. A third temperature sensor can be connected to one of it’s digital input for either defrost
management of second evaporator; condenser temperature control or to activate economic set point.
Other salient features include hour-meter to clock the working hours of compressor for preventive
maintenance, internal buzzer, IP65 frontal, min-max temperature record, temperature sensor response
time control, fast freezing mode, tamper-proof function, control functions shutdown and RS485 serial
communication port for Sitrad real-time monitoring and management.
Product conforming to UL Inc. (United States and Canada) and NSF (United States).
2. APPLICATION
Walk-in freezers
Display freezers
Upright freezers
evolution
V
er.03
TC-900e Log
5. INSTALLATION - ASSEMBLING AND ELECTRICAL
CONNECTIONS
Control
functions
shutdown
Functions
lockdown
Serial
programming
Protection
level
IP 65
FRONT
Fast
Freezing
Datalogger
LOG
Supervisory
system
3. TECHNICAL SPECIFICATIONS
Power supply
Control temperature
Operating humidity
Dimensions (mm)
76 x 34 x 77 mm (WxHxD)
Dimensions of the clipping for fixing
of the instrument
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
TC-900E Log: 115 or 230Vac ±10% (50/60Hz)
TC-900EL Log: 12 or 24Vac/dc +10%
-50°C to 105°C / -58°F to 221°F
Operating temperature
0 to 50°C / 32 to 122°F
Load current (outputs)
COMP: 12(8)A / 240Vac 1HP
DEFR: 10A / 240Vac 2400W
FANS: 5(3)A / 240Vac
10 to 85 %RH (without condensation)
Defrost indication LED
Temperature unit indication LED
Control functions shutdown indication LED
TC-900e Log
Upper key
Lower key
Set key
Quick Access
Menu Key
Functions lockdown indication LED
Compressor output
indication LED
Fan indication LED
6.2 Quick access keys map
When the controller is on temperature display, the following keys serve as a shortcut for the following
functions:
/
<
<
<
<
Hold down for 2 seconds: setpoint adjustment.
Short touch: displays the current process.
Short touch: displays the maximum and minimum measurements recorded.
Hold down for 10 seconds: manual datalogger activation.
<
Hold down for 2 seconds: inhibits the audible alarm.
<
Hold down for 2 seconds: clears history when records are displayed.
;
Short touch: enter the quick access menu.
and
<
Hold down for 4 seconds: carries out manual defrost.
/
Short touch: the current day, month, year, day of the week, hour, and
minute will be shown in sequence on the display.
<
<
Short touch: Go to menu selection.
and
71 mm± 0,5
29 mm± 0,5
Panel (Front View)
Panel
(Side View)
Dimension of the clipping
for fixing of the
instrument in panel
ATTENTION
FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO AVOID LIQUID CONTACT, THE CUT FOR THE CONTROLLER MUST BE OF
70,5X29mm MAXIMUM. THE SIDE LOCKS MUST BE FIXED SO IT PRESSES THE RUBBER SEALING AVOIDING
INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.
IMPORTANT
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER TERMINALS;
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:
<
Hold down for 2 seconds: resets the counter when the hour meter is being
displayed.
Maximum consumption of device
1.5 VA
Luminosity
sensor
Hourmeter
TC-900e Log
TC-900e Log
Connection 115 Vac
1
5
6
7
8
2
3
4
9 10
11 12
13
14
15 16
17
S1
D2
S2
COMP
DEFR
115 Vac
FANS /
DEFR 2
A
B
SITRAD
D1/S3
1
5
6
7
8
2
3
4
9 10
11 12
13
14
15 16
17
230 Vac
COMP
DEFR
FANS /
DEFR 2
Connection 230 Vac
D2
A
B
SITRAD
S1
S2
D1/S3
The sensor S1 (black) must be in the ambient.
The sensor S2 (gray) must be placed in the evaporator
through metallic cramp.
LEGEND:
To the terminal of
the connecting block
Connection 12 Vac/dc
1
5
6
7
8
2
3
4
9 10
11 12
13
14
15 16
17
COMP
DEFR
FANS /
DEFR 2
12 Vac/dc
D2
A
B
SITRAD
Loads supply
S1
S2
D1/S3
1
5
Connection 24 Vac/dc
6
7
8
2
3
4
9 10
11 12
13
14
15 16
17
COMP
DEFR
FANS /
DEFR 2
24 Vac/dc
D2
A
B
SITRAD
S1
S2
D1/S3
Loads supply
E251415
COMPONENT
Have this manual in the palm of
your hand by FG Finder application.
TC900ELOGV03-01T-16578
Pressed for 5 seconds: turn on/turn off the control functions.
;
FAST FREEZING (ON/OFF)
;
TC-900e Log
;
ECONOMIC SETPOINT (ON/OFF)
TC-900e Log
;
DEFROST (ON/OFF)
TC-900e Log
;
FUNCTIONS LOCKDOWN
TC-900e Log
;
CONTROL FUNCTIONS
SHUTDOWN (ON/OFF)
TC-900e Log
NORMAL SETPOINT
;
TC-900e Log
ERASE MIN. AND MAX.
VALUES
;
TC-900e Log
EXIT FUNCTION
;
TC-900e Log
ECONOMIC SETPOINT
;
TC-900e Log
FUNCTION SELECTION
;
TC-900e Log
MIN. AND MAX.
TEMPERATURE RECORD
;
TC-900e Log
DISPLAY TIME AND DATE
TC-900e Log
;
ON/OFF DATA LOGGER
(MANUAL MODE)
TC-900e Log
;
;
TC-900e Log
DISPLAY HOURMETER
RESET HIGH AND LOW
PRESSURE ALARMS
;
TC-900e Log
Question and Answer IconNeed help?

Do you have a question about the Full Gauge TC-900E Log and is the answer not in the manual?

Full Gauge TC-900E Log Specifications

General IconGeneral
Power Supply115 or 230 Vac ±10% (50/60 Hz)
Data LoggingYes
Resolution0.1°C
Sensor TypeNTC
Operating Temperature0 to 50°C
Relay Output (Defrost)10A/250V AC
ProtectionIP65 on the front panel
Accuracy±1°C

Summary

Controller Description, Application, and Specifications

Technical Specifications Overview

Lists power supply, temperature ranges, load currents, dimensions, and operating conditions.

Installation and Electrical Connections

Installation Safety and Tools

Provides crucial warnings for sealing, liquid contact, and tool usage for terminals.

Controller Operations and Features

Operating Modes: Basic vs. Advanced

Explains the difference between basic and advanced operating modes and their features.

Adjusting Temperature Setpoints

Describes how to adjust normal and economic setpoints using the controller keys.

Fast Freezing Mode Operation

Details the activation, deactivation, and behavior of the fast freezing function.

Economic Setpoint (SPE) Functionality

Explains how the economic setpoint works and how to activate/deactivate it.

Manual Defrost Procedure

Describes how to manually activate or deactivate the defrost cycle using keys or inputs.

Determining Defrost End by Temperature

Guides on configuring parameters to end defrost based on evaporator temperature.

Functions Lock Security Feature

Details how to activate and use the functions lock to prevent parameter changes.

Control Functions Shutdown Mode

Explains how to disable control functions, leaving the controller as an indicator.

Minimum and Maximum Temperature Records

Explains how to view and clear recorded minimum and maximum temperatures.

Manual Datalogger Activation

Explains how to manually start or stop the internal data logger.

Advanced Operations and Settings

Access Code for Parameters

How to enter the access code to change controller parameters and clock.

Changing Controller Parameters

Step-by-step guide to navigate and modify controller functions and parameters.

Adjusting Date and Time

Instructions for setting the controller's internal clock and date.

Defrost Schedule Configuration

Details on setting up defrost schedules by day of the week and time.

Internal Datalogger Configuration

Explains how to configure the datalogger to store temperature and state records.

Economic Setpoint Activation Sensor Configuration

How to configure the light intensity sensor to activate the economic setpoint.

Controller Parameter Table (Part 1)

Parameter F00: Controller Operating Mode

Configures the controller for basic (30 functions) or advanced (76 functions) operation.

Parameter F01: Defrost Schedule Programming

Enables and configures time-based defrost schedules for the controller.

Controller Parameter Table (Part 2)

Parameter F08: Refrigeration Interval

Establishes the maximum cooling time before starting the next defrost cycle.

Parameter F13: Defrost End Temperature

Sets the evaporator temperature threshold to end the defrost cycle.

Parameter F14: Maximum Defrost Time

Defines the maximum duration for a defrost cycle to prevent issues if temperature fails.

Parameter F24: RS-485 Network Address

Assigns the controller's unique address for communication with Sitrad software.

Controller Parameter Table (Part 3)

Parameter F31: Normal Setpoint

Defines the desired room temperature for normal operation.

Parameter F32: Economic Setpoint (SPE)

Defines the desired room temperature for economy mode operation.

Parameter F45: Defrost Start Condition

Selects defrost start condition: time-based or temperature-based.

Controller Parameter Table (Part 4)

Parameter F47: Evaporator Temp. to Start Defrost

Sets the evaporator temperature threshold that triggers defrost initiation.

Parameter F57: Digital Input 1 / Sensor S3 Function

Configures the function of digital input 1, which can also act as sensor S3.

Parameter F58: Digital Input 2 Function

Configures the function of digital input 2.

Parameter F62: Function Lock Configuration

Configures the function lock to protect parameters from unauthorized changes.

Parameter F64: Control Functions Shutdown

Authorizes switching off the control functions for indicator-only operation.

Parameter F66: Max Compressor Operating Time for Maintenance

Sets the compressor operating time limit for triggering a maintenance warning.

Controller Signal and Alarm Indications

Signal AL-C: Compressor Maintenance Alert

Indicates that the compressor has reached its maximum operating time for maintenance.

Signal APLO: Low Pressure Alarm

Indicates a low pressure alarm that requires manual reset.

Signal APH.: High Pressure Alarm

Indicates a high pressure alarm that requires manual reset.

Integrating Controllers with RS-485 and Computer

Sitrad Software for Monitoring and Management

Information on using Sitrad software for real-time monitoring and management via RS-485.

RS-485 Network Wiring and Interface

Details on connecting multiple controllers via RS-485 network and interface.

Full Gauge Controls Warranty Information

How to Use the Warranty Service

Explains the procedure for submitting a product for warranty service.

Related product manuals