Electric IOM
Installation
12
Model FB-L 012 015 018 024 030 036 050 075 100 150 200 300 500 750 1000
Unit Size: kW 12 15 18 24 30 36 50 75 100 150 200 300 500 750 1000
HP 1.2 1.5 1.8 2.4 3.0 3.5 5.0 7.5 10 15 20 30 50 75 100
(A) Horizontal IN 14 14 14 14 14 14 -- -- -- -- -- -- -- -- --
to remove elements MM 356 356 356 356 356 356 -- -- -- -- -- -- -- -- --
(B) Floor to Ceiling IN -- -- -- -- -- -- 95 95 95 95 95 139 139 139 139
to remove elements MM -- -- -- -- -- -- 2413 2413 2413 2413 2413 3531 3531 3531 3531
(C) Front of Boiler* IN 24 24 24 24 24 24 24 32 32 32 34 34 36 36 36
MM 610 610 610 610 610 610 610 813 813 813 864 864 914 914 914
(D) Sides & Rear of Boiler IN 12 12 12 12 12 12 12 12 12 12 24 24 24 24 24
MM 305 305 305 305 305 305 305 305 305 305 610 610 610 610 610
*This represents the door clearance. UL requires at least 36” clearance in front of any electrical control panel