6K/10K Rack/Tower Online UPS
Uninterruptible Power Supply System
Version: 1.2
User Manual

Questions and Answers

  • M
    Mr. Joshua MillerAug 20, 2025
    What to do if my Galleon 6KRT shows an overload?
    • K
      kathleen99Aug 20, 2025
      If your Galleon UPS indicates an overload, it means the load is too heavy. Remove excess loads from the UPS output. If the overload time exceeds the specification, the UPS will shut down automatically; in this case, remove excess loads and restart the UPS.
  • Q
    qgreeneAug 22, 2025
    Why is my Galleon 6KRT beeping and showing 'Batt Low'?
    • M
      Michael AndersonAug 22, 2025
      If your Galleon UPS displays a 'Batt Low' warning, it could be due to several reasons: the battery may be deeply discharged, the battery number setting might be incorrect, or the battery may be at the end of its life. Try recharging the battery first. If that doesn't work, check and correct the battery number setting. If the problem persists, the battery likely needs replacement.
  • E
    Elizabeth RodriguezAug 23, 2025
    What to do if my Galleon 6KRT says 'Over Temp'?
    • S
      Sarah HullAug 25, 2025
      If your Galleon UPS displays an 'Over Temp' warning, the internal temperature is too high. This could be due to a hot environment, a blocked or failed fan, blocked ventilation, or an excessive load. Ensure the ambient temperature is not over 40ÂșC, check the fan, ensure proper ventilation, and remove some loads if possible.
  • D
    Dale SanchezAug 26, 2025
    How to fix a 'Batt Open' error on my Galleon 6KRT?
    • D
      David WatsonAug 26, 2025
      A 'Batt Open' error on your Galleon UPS indicates that the battery is not connected properly or the battery protection device is open. Ensure the battery is well connected. If it is, the protection device may need to be replaced or restored.
  • L
    Lauren MillerAug 28, 2025
    What causes an 'Over Charge' error on a Galleon UPS?
    • V
      Vanessa StewartAug 28, 2025
      An 'Over Charge' error on your Galleon UPS can be caused by incorrect battery number settings or a charger voltage that is too high. Correct the battery number or its setting. Also, disconnect the battery and check the charger output voltage. Contact the dealer to repair the charger if it has failed.
  • S
    Susan GrantAug 29, 2025
    What to do if my Galleon 6KRT displays 'Fan Error'?
    • J
      Jessica VelezAug 29, 2025
      If your Galleon UPS shows a 'Fan Error', the fan might be blocked or at the end of its life, or the fan detection circuit may have failed. First, ensure the fan is not blocked. If the fan isn't blocked, contact the dealer to replace the fan or repair the detection circuit.
  • M
    Meagan RollinsSep 1, 2025
    What does 'EPO Enable' mean on my Galleon UPS and how to fix it?
    • D
      Douglas CalhounSep 1, 2025
      If your Galleon UPS displays 'EPO Enable', it means the EPO plug (jumper) is removed or the external EPO switch is off. Connect the EPO plug (jumper) or switch on the external EPO switch.
  • M
    Miranda WarrenSep 3, 2025
    What to do if my Galleon 6KRT UPS displays 'Overload 3Times'?
    • S
      Samantha RobinsonSep 3, 2025
      If your Galleon UPS displays 'Overload 3Times', it has locked in bypass after experiencing an overload three times in 30 minutes. Remove excess loads from the UPS output, then shut down the UPS and restart it.
  • D
    David JohnsonSep 5, 2025
    What does 'Para Comm Fail' mean on my Galleon 6KRT UPS and how to fix it?
    • W
      William ReedSep 5, 2025
      If your Galleon UPS displays 'Para Comm Fail', it indicates that the parallel cable for communication is not connected well in the parallel system. Connect the parallel cable securely.
  • S
    swansonjamesSep 7, 2025
    What does 'Output Short' mean on my Galleon 6KRT UPS and how to resolve it?
    • X
      xmcculloughSep 7, 2025
      If your Galleon UPS indicates 'Output Short', a short circuit has occurred on the UPS output. Remove the short circuit.