ANSI/SIA CP-01 requirements
CP-01 feature descriptions and specifications are listed in Table 9. The following are requirements for compliance with ANSI/SIA
CP-01 standards.
Note: Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.
Minimum system requirements:
One control panel
Two keypads
Do not enable remote arming in SIA classified installations.
Off premise transmission must be in the SIA format.
Do not exceed 1 minute for the abort window and entry delay.
Note: A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station.
Table 9. CP-01 feature descriptions and specifications
CP-01 feature description Feature description as shown in
manual
Program
location
Seg/opt Default CP-01 required setting
Exit time Exit 1 delay 24 2 60 45 to 240 seconds
Exit 2 delay 24 4 60 45 to 240 seconds
Progress annunciation / disable -
for silent exit
Silent keypad option 93
a
a. Refer to your keypad installation manual.
2 All annunciators
enabled
Allowed (individual keypads
may be disabled)
Exit time restart (reexit) This feature is not programmable in the panel. Enabled
Auto stay arm on unvacated
premises
Auto bypass 23 1/3 Enabled Enabled
Exit time and progress annuncia-
tion/disable for remote arm
This feature is not programmable in the panel. Exit time and progress are always enabled. Enabled (disabled for remote
arming)
Entry delays
b
b. Combined abort window time and entry delay must not exceed one minute.
Entry 1 delay 24 1 30 30 to 240 seconds
Entry 2 delay 24 3 30 30 to 240 seconds
Abort window - for
nonfire zones
Dialer delay 40 8 30 Enabled (may be disabled by
zone/zone type, but no cancel
reports will be sent)
Abort window time - for nonfire
zones
b
Dialer delay 40 8 30 15 to 45 seconds
Abort annunciation This feature is not programmable in the panel. Flashing cancel LED goes off when
disarming.
Enabled
Cancel annunciation Cancel 23 3/6 Enabled Enabled
Duress feature Duress 44 Disabled Disabled
Cross zoning Two trips on cross zone 37 5/4 Disabled Required
Keypad sounds on cross zone trip 39 5 Disabled
Zone type characteristic 111 3/4 Disabled
Programmable cross zoning time Cross zone time 40 6 5 minutes Allowed
Swinger shutdown Swinger shutdown count 38 n/a Enabled for 1 trip For all nonfire zones, shut
down at 1 to 2 trips
Swinger shutdown disable Swinger shutdown count 38 n/a Enabled for 1 trip Allowed
Fire alarm verification Fire alarm verification time 40 9 Disabled Required (depends on panel
and sensors)
Call waiting cancel Must be programmed as part of the
phone number
0 n/a n/a Required (depends on user
phone line)
Default changes (from prior
versions):
Recent closing 23 3/7 Enabled
Exit error 23 3/8 Enabled
Power up delay 40 3 60 seconds