18 489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
 
0466 Neutral Voltage Angle 0 to 359 1 – F1 0
METERING DATA / POWER METERING
0480 Power Factor –100 to 100 1 – F6 0
0481 Real Power –2000000 to 2000000 1 MW F13 0
0483 Reactive Power –2000000 to 2000000 1 Mvar F13 0
0485 Apparent Power –2000000 to 200000 1 MVA F13 0
0487 Positive Watthours 0 to 4000000000 1 MWh F13 0
0489 Positive Varhours 0 to 4000000000 1 Mvarh F13 0
048B Negative Varhours 0 to 4000000000 1 Mvarh F13 0
METERING DATA / TEMPERATURE
04A0 Hottest Stator RTD 1 to 12 1 – F1 0
04A1 Hottest Stator RTD Temperature –52 to 250 1 °C F4 –52
04A2 RTD #1 Temperature –52 to 251 1 °C F4 –52
04A3 RTD #2 Temperature –52 to 251 1 °C F4 –52
04A4 RTD #3 Temperature –52 to 251 1 °C F4 –52
04A5 RTD #4 Temperature –52 to 251 1 °C F4 –52
04A6 RTD #5 Temperature –52 to 251 1 °C F4 –52
04A7 RTD #6 Temperature –52 to 251 1 °C F4 –52
04A8 RTD #7 Temperature –52 to 251 1 °C F4 –52
04A9 RTD #8 Temperature –52 to 251 1 °C F4 –52
04AA RTD #9 Temperature –52 to 251 1 °C F4 –52
04AB RTD #10 Temperature –52 to 251 1 °C F4 –52
04AC RTD #11 Temperature –52 to 251 1 °C F4 –52
04AD RTD #12 Temperature –52 to 251 1 °C F4 –52
04C0 Hottest Stator RTD Temperature –52 to 250 1 °F F4 –52
04C1 RTD #1 Temperature –52 to 251 1 °F F4 –52
04C2 RTD #2 Temperature –52 to 251 1 °F F4 –52
04C3 RTD #3 Temperature –52 to 251 1 °F F4 –52
04C4 RTD #4 Temperature –52 to 251 1 °F F4 –52
04C5 RTD #5 Temperature –52 to 251 1 °F F4 –52
04C6 RTD #6 Temperature –52 to 251 1 °F F4 –52
04C7 RTD #7 Temperature –52 to 251 1 °F F4 –52
04C8 RTD #8 Temperature –52 to 251 1 °F F4 –52
04C9 RTD #9 Temperature –52 to 251 1 °F F4 –52
04CA RTD #10 Temperature –52 to 251 1 °F F4 –52
04CB RTD #11 Temperature –52 to 251 1 °F F4 –52
04CC RTD #12 Temperature –52 to 251 1 °F F4 –52
METERING DATA / DEMAND METERING
04E0 Current Demand 0 to 1000000 1 Amps F12 0
04E2 MW Demand 0 to 2000000 1 MW F13 0
04E4 Mvar Demand 0 to 2000000 1 Mvar F13 0
04E6 MVA Demand 0 to 2000000 1 MVA F13 0
04E8 Peak Current Demand 0 to 1000000 1 Amps F12 0
04EA Peak MW Demand 0 to 2000000 1 MW F13 0
04EC Peak Mvar Demand 0 to 2000000 1 Mvar F13 0
04EE Peak MVA Demand 0 to 2000000 1 MVA F13 0
METERING DATA / ANALOG INPUTS
0500 Analog Input 1 –50000 to 50000 1 Units F12 0
0502 Analog Input 2 –50000 to 50000 1 Units F12 0
0504 Analog Input 3 –50000 to 50000 1 Units F12 0
0506 Analog Input 4 –50000 to 50000 1 Units F12 0
METERING DATA / SPEED
0520 Tachometer 0 to 7200 1 RPM F1 0
Table CG–1: 489 Memory Map (Sheet 6 of 30)
ADDR Name RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page page 42