22 489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
11C5 Generator Phase Sequence 0 to 2 1 F124 0
SYSTEM SETUP / SERIAL START/STOP
11E0 Serial Start/Stop Initiation 0 to 1 1 F105 0
11E1 Startup Initiation Relays (2-5) 1 to 4 1 F50 0
11E2 Shutdown Initiation Relays (1-4) 0 to 3 1 F50 0
11E3 Serial Start/Stop Events 0 to 1 1 F105 0
DIGITAL INPUTS / BREAKER STATUS
1200 Breaker Status 0 to 1 1 F209 1
DIGITAL INPUTS / GENERAL INPUT A
1210 Assign Digital Input 0 to 7 1 F210 0
1211 Asserted Digital Input State 0 to 1 1 F131 0
1212 Input Name 0 to 12 1 F22 _
1218 Block Input From Online 0 to 5000 1 s F1 0
1219 General Input A Control 0 to 1 1 F105 0
121A Pulsed Control Relay Dwell Time 0 to 250 1 s F2 0
121B Assign Control Relays (1-5) 0 to 4 1 F50 0
121C General Input A Control Events 0 to 1 1 F105 0
121D General Input A Alarm 0 to 2 1 F115 0
121E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
121F General Input A Alarm Delay 1 to 50000 1 s F2 50
1220 General Input A Alarm Events 0 to 1 1 F105 0
1221 General Input A Trip 0 to 2 1 F115 0
1222 Assign Trip Relays (1-4) 0 to 3 1 F50 1
1223 General Input A Trip Delay 1 to 50000 1 s F2 50
DIGITAL INPUTS / GENERAL INPUT B
1230 Assign Digital Input 0 to 7 1 F210 0
1231 Asserted Digital Input State 0 to 1 1 F131 0
1232 Input Name 0 to 12 1 F22 _
1238 Block Input From Online 0 to 5000 1 s F1 0
1239 General Input B Control 0 to 1 1 F105 0
123A Pulsed Control Relay Dwell Time 0 to 250 1 s F2 0
123B Assign Control Relays (1-5) 0 to 4 1 F50 0
123C General Input B Control Events 0 to 1 1 F105 0
123D General Input B Alarm 0 to 2 1 F115 0
123E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
123F General Input B Alarm Delay 1 to 50000 1 s F2 50
1240 General Input B Alarm Events 0 to 1 1 F105 0
1241 General Input B Trip 0 to 2 1 F115 0
1242 Assign Trip Relays (1-4) 0 to 3 1 F50 1
1243 General Input B Trip Delay 1 to 50000 1 s F2 50
DIGITAL INPUTS / GENERAL INPUT C
1250 Assign Digital Input 0 to 7 1 F210 0
1251 Asserted Digital Input State 0 to 1 1 F131 0
1252 Input Name 0 to 12 1 F22 _
1258 Block Input From Online 0 to 5000 1 s F1 0
1259 General Input C Control 0 to 1 1 F105 0
125A Pulsed Control Relay Dwell Time 0 to 250 1 s F2 0
125B Assign Control Relays (1-5) 0 to 4 1 F50 0
125C General Input C Control Events 0 to 1 1 F105 0
125D General Input C Alarm 0 to 2 1 F115 0
125E Assign Alarm Relays (2-5) 1 to 4 1 F50 16
125F General Input C Alarm Delay 1 to 50000 1 s F2 50
1260 General Input C Alarm Events 0 to 1 1 F105 0
Table CG–1: 489 Memory Map (Sheet 10 of 30)
ADDR Name RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page page 42