24 489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
12D1 Asserted Digital Input State 0 to 1 1 F131 0
12D2 Input Name 0 to 12 1 F22 _
12D8 Block Input From Online 0 to 5000 1 s F1 0
12D9 General Input G Control 0 to 1 1 F105 0
12DA Pulsed Control Relay Dwell Time 0 to 250 1 s F2 0
12DB Assign Control Relays (1-5) 0 to 4 1 F50 0
12DC General Input G Control Events 0 to 1 1 F105 0
12DD General Input G Alarm 0 to 2 1 F115 0
12DE Assign Alarm Relays (2-5) 1 to 4 1 F50 16
12DF General Input G Alarm Delay 1 to 50000 1 s F2 50
12E0 General Input G Alarm Events 0 to 1 1 F105 0
12E1 General Input G Trip 0 to 2 1 F115 0
12E2 Assign Trip Relays (1-4) 0 to 3 1 F50 1
12E3 General Input G Trip Delay 1 to 50000 1 s F2 50
DIGITAL INPUTS / REMOTE RESET
1300 Assign Digital Input 0 to 7 1 F210 0
DIGITAL INPUTS / TEST INPUT
1310 Assign Digital Input 0 to 7 1 F210 0
DIGITAL INPUTS / THERMAL RESET
1320 Assign Digital Input 0 to 7 1 F210 0
DIGITAL INPUTS / DUAL SETPOINTS
1340 Assign Digital Input 0 to 7 1 F210 0
1341 Active Setpoint Group 0 to 1 1 F118 0
1342 Edit Setpoint Group 0 to 1 1 F118 0
DIGITAL INPUTS / SEQUENTIAL TRIP
1360 Assign Digital Input 0 to 7 1 F210 0
1361 Sequential Trip Type 0 to 1 1 F206 0
1362 Assign Trip Relays (1-4) 0 to 3 1 F50 1
1363 Sequential Trip Level 2 to 99 1 × Rated MW F14 5
1365 Sequential Trip Delay 2 to 1200 1 s F2 10
DIGITAL INPUTS / FIELD-BREAKER DISCREPANCY
1380 Assign Digital Input 0 to 7 1 F210 0
1381 Field Status Contact 0 to 1 1 F109 0
1382 Assign Trip Relays (1-4) 0 to 3 1 F50 1
1383 Field-Breaker Discrepancy Trip Delay 1 to 5000 1 s F2 10
DIGITAL INPUTS / TACHOME TER
13A0 Assign Digital Input 0 to 7 1 F210 0
13A1 Rated Speed 100 to 3600 1 RPM F1 3600
13A2 Tachometer Alarm 0 to 2 1 F115 0
13A3 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
13A4 Tachometer Alarm Speed 101 to 175 1 %Rated F1 110
13A5 Tachometer Alarm Delay 1 to 250 1 s F1 1
13A6 Tachometer Alarm Events 0 to 1 1 F105 0
13A7 Tachometer Trip 0 to 2 1 F115 0
13A8 Assign Trip Relays (1-4) 0 to 3 1 F50 1
13A9 Tachometer Trip Speed 101 to 175 1 %Rated F1 110
13AA Tachometer Trip Delay 1 to 250 1 s F1 1
DIGITAL INPUTS / WAVEFORM CAPTURE
13C0 Assign Digital Input 0 to 7 1 F210 0
DIGITAL INPUTS / GROUND SWITCH STATUS
13D0 Assign Digital Input 0 to 7 1 F210 0
13D1 Ground Switch Contact 0 to 1 1 F109 0