32 489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
220F Negative Mvar Trip Delay 2 to 1200 1 s F2 10
2210 Positive Mvar Trip Delay 2 to 1200 1 s F2 200
2211 Positive Mvar Alarm Delay 2 to 1200 1 s F2 100
POWER ELEMENTS / REVERSE POWER
2240 Block Reverse Power From Online 0 to 5000 1 s F1 1
2241 Reverse Power Alarm 0 to 2 1 F115 0
2242 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2243 Reverse Power Alarm Level 2 to 99 1 × Rated F14 5
2245 Reverse Power Alarm Delay 2 to 1200 1 s F2 100
2246 Reverse Power Alarm Events 0 to 1 1 F105 0
2247 Reverse Power Trip 0 to 2 1 F115 0
2248 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2249 Reverse Power Trip Level 2 to 99 1 × Rated F14 5
224B Reverse Power Trip Delay 2 to 1200 1 s F2 200
POWER ELEMENTS / LOW FORWARD POWER
2280 Block Low Forward Power From Online 0 to 15000 1 s F1 0
2281 Low Forward Power Alarm 0 to 2 1 F115 0
2282 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2283 Low Forward Power Alarm Level 2 to 99 1 × Rated MW F14 5
2285 Low Forward Power Alarm Delay 2 to 1200 1 s F2 100
2286 Low Forward Power Alarm Events 0 to 1 1 F105 0
2287 Low Forward Power Trip 0 to 2 1 F115 0
2288 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2289 Low Forward Power Trip Level 2 to 99 1 × Rated MW F14 5
228B Low Forward Power Trip Delay 2 to 1200 1 s F2 200
RTD TEMPERATURE / RTD TYPES
2400 Stator RTD Type 0 to 3 1 F120 0
2401 Bearing RTD Type 0 to 3 1 F120 0
2402 Ambient RTD Type 0 to 3 1 F120 0
2403 Other RTD Type 0 to 3 1 F120 0
RTD TEMPERATURE / RTD #1
2420 RTD #1 Application 0 to 4 1 F121 1
2421 RTD #1 Alarm 0 to 2 1 F115 0
2422 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2423 RTD #1 Alarm Temperature 1 to 250 1 °C F1 130
2424 RTD #1 Alarm Events 0 to 1 1 F105 0
2425 RTD #1 Trip 0 to 2 1 F115 0
2426 RTD #1 Trip Voting 1 to 12 1 F122 1
2427 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2428 RTD #1 Trip Temperature 1 to 250 1 °C F1 155
2429 RTD #1 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #2
2460 RTD #2 Application 0 to 4 1 F121 1
2461 RTD #2 Alarm 0 to 2 1 F115 0
2462 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2463 RTD #2 Alarm Temperature 1 to 250 1 °C F1 130
2464 RTD #2 Alarm Events 0 to 1 1 F105 0
2465 RTD #2 Trip 0 to 2 1 F115 0
2466 RTD #2 Trip Voting 1 to 12 1 F122 2
2467 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2468 RTD #2 Trip Temperature 1 to 250 1 °C F1 155
2469 RTD #2 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #3
Table CG–1: 489 Memory Map (Sheet 20 of 30)
ADDR Name RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page page 42