1.1.18 Mains Supply 1 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]
0.18 0.37 0.75 1.5 2.2
Typical Shaft Output [HP] 0.25 0.5 1 2 3
IP 20
Unit Size
M1
Unit Size M1 Unit Size
M1
Unit Size
M2
Unit Size
M3
Output current
Continuous (1 x 200-240 V ) [A] 1.2 2.2 4.2 6.8 9.6
Intermittent (1 x 200-240 V ) [A] 1.8 3.3 6.3 10.2 14.4
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (1 x 200-240 V ) [A] 3.3 6.1 11.6 18.7 26.4
Intermittent (1 x 200-240 V ) [A] 4.5 8.3 15.6 26.4 37.0
Max. mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/Typ-
ical
1)
12.5/
15.5
20.0/
25.0
36.5/
44.0
61.0/
67.0
81.0/
85.1
Weight enclosure IP20 [kg] 1.1 1.1 1.1 1.6 3.0
Efficiency [%], Best case/Typical
1)
95.6/
94.5
96.5/
95.6
96.6/
96.0
97.0/
96.7
96.9/
97.1
Table 1.6: Mains supply 1 x 200 - 240 VAC
1. At rated load conditions.
1.1.19 Mains Supply 3 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW]
0.25 0.37 0.75 1.5 2.2 3.7
Typical Shaft Output [HP] 0.33 0.5 1 2 3 5
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 200-240 V ) [A] 1.5 2.2 4.2 6.8 9.6 15.2
Intermittent (3 x 200-240 V ) [A] 2.3 3.3 6.3 10.2 14.4 22.8
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
Max. input current
Continuous (3 x 200-240 V ) [A] 2.4 3.5 6.7 10.9 15.4 24.3
Intermittent (3 x 200-240 V ) [A] 3.2 4.6 8.3 14.4 23.4 35.3
Max.mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
14.0/
20.0
19.0/
24.0
31.5/
39.5
51.0/
57.0
72.0/
77.1
115.0/
122.8
Weight enclosure IP20 [kg] 1.1 1.1 1.1 1.6 3.0 3.0
Efficiency [%], Best case/Typical
1)
96.4/
94.9
96.7/
95.8
97.1/
96.3
97.4/
97.2
97.2/
97.4
97.3/
97.4
Table 1.7: Mains supply 3 x 200 - 240 VAC
1. At rated load conditions.