1.1.11 Electrical Installation in General
NB!
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (60-75r C) rec-
ommended.
Details of terminal tightening torques.
Power (kW) Torque (Nm)
Unit Size 1 x 200-240 V 3 x 200-240 V 3 x 380-480 V Line Motor DC connection/Brake Control Terminals Earth Relay
M1 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 1.4 0.7
Spade
1)
0.15 3 0.5
M2 1.5 1.5 1.5 - 2.2 1.4 0.7
Spade
1)
0.15 3 0.5
M3 2.2 2.2 - 3.7 3.0 - 7.5 1.4 0.7
Spade
1)
0.15 3 0.5
M4 11.0-15.0 1.3 1.3 1.3 0.15 3 0.5
M5 18.5-22.0 1.3 1.3 1.3 0.15 3 0.5
1)
Spade connectors (6.3 mm Faston plugs)
Table 1.2: Tightening of terminals.
1.1.12 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short circuit protection:
GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 480 V maximum.
Overcurrent protection:
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national
regulations.
Non UL compliance:
If UL/cUL is not to be complied with, GE recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter.
AF-60 LPറ Micro Drive