[26] Precise stop inverse (on-
ly terminal 33)
Prolong the stop signal to give a precise stop independent of scan time. The function is available for terminal 33 only.
[27] Start, precise stop (only
terminal 33)
As [26], but including Start.
[28] Catch up Select Catch up/Slow down to increase or reduce the resulting reference value by the percentage set in par. 3-12.
[29] Slow down Same as Catch up [28]
[32] Pulse input (only termi-
nal 33)
Select Pulse input when using a pulse sequence as either reference or feedback. Scaling is done in par. group 5-5*.
[34] Ramp bit 0 Logic 0 = Ramp1, see par. 3-4*.
Logic 1 = Ramp2, see par. 3-5*.
[60] Counter A (up) Input for counter A.
[61] Counter A (down) Input for counter A.
[62] Reset counter A Input for reset of counter A.
[63] Counter B (up) Input for counter B.
[64] Counter B (down) Input for counter B.
[65] Reset counter B Input for reset of counter B.
5-10 Terminal 18 Digital Input
Option: Function:
[8]
*
Start Select function from available digital input range.
See par. 5-1* for choices.
5-11 Terminal 19 Digital Input
Option: Function:
[10]
*
Reversing Select function from available digital input range.
See par. 5-1* for choices.
5-12 Terminal 27 Digital Input
Option: Function:
[1]
*
Reset Select function from available digital input range.
See par. 5-1* for choices.
5-13 Terminal 29 Digital Input
Option: Function:
[14]
*
Jog Select function from available digital input range.
See par. 5-1* for choices.
5-15 Terminal 33 Digital Input
Option: Function:
[16]
*
Preset bit 0 Select function from available digital input range.
See par. 5-1* for choices.
4.6.3. 5-4* Relays
Parameter group for configuring timing and output functions for relays.
[0] No Operation Default for all digital and relay outputs.
[1] Control Ready Control board receives supply voltage.
[2] Drive Ready Frequency converter is ready for operation and applies supply signal on control board.
[3] Drive Ready, Remote Frequency converter is ready for operation in Auto mode.
[4] Enable/No Warning Frequency converter is ready for operation. No start or stop command is given. No warnings are present.
[5] Drive Running Motor is running.
[6] Running/No Warning Motor runs, and no warning are present.