5. Parameter Lists
Parameter Overwiev
0-** Operation/Display
0-0* Basic Settings
0-03 Regional Settings
[0] International
*[1] US
0-04 Oper. State at Power-up (Hand)
[0] Resume
*[1] Forced stop, ref = old
[2] Forced stop, ref = 0
0-1* Set-up Handling
0-10 Active Set-up
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Set-up
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00 – 9999.00
*0.00
0-32 Custom Readout Max Scale
0.00 – 9999.00
*100.0
0-4* Keypad
0-40 [Hand] Key on Keypad
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on Keypad
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto] Key on Keypad
[0] Disabled
*[1] Enabled
0-5* Copy/Save
0-50 Keypad Copy
*[0] No copy
[1] All to Keypad
[2] All from Keypad
[3] Size indep. from Keypad
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6* Password
0-60 (Main) Menu Password
0 - 999 * 0
1-** Load/Motor
1-0* General Settings
1-00 Configuration Mode
*[0] Speed open loop
[3] Process
1-01 Motor Control Principle
[0] U/f
*[1] Adv.Vector Control
1-03 Torque Characteristics
*[0] Constant torque
[2] Energy Saving
1-05 Local Mode Configuration
[0] Speed Open Loop
*[2] As config in param. 1-00
1-2* Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18 kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37 kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.00 HP
[16] 11.00 kW/15.00 HP
1-22 Motor Voltage
50 - 999 V * 230 - 400 V
1-23 Motor Frequency
20 - 400 Hz * 60 Hz
1-24 Motor Current
0.01 - 26.00 A * Motortype dep.
1-25 Motor Nominal Speed
100 - 9999 rpm * Motortype dep.
1-29 Auto Tune
*[0] Off
[2] Enable Auto Tune
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance (X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5* Load Indep. Setting
1-50 Motor Magnetisation at 0 Speed
0 - 300 % * 100 %
1-52 Min Speed Norm. Magnet. [Hz]
0.0 - 10.0 Hz * 0.0 Hz
1-55 U/f Characteristic - U
0 - 999.9 V
1-56 U/f Characteristic - F
0 - 400 Hz
1-6* Load Depen. Setting
1-60 Low Speed Load Compensation
0 - 199 % * 100 %
1-61 High Speed Load Compensation
0 - 199 % * 100 %
1-62 Slip Compensation
-400 - 399 % * 100 %
1-63 Slip Compensation Time Constant
0.05 - 5.00 s * 0.10 s
1-7* Start Adjustments
1-71 Holding Time
0.0 - 10.0 s * 0.0 s
1-72 Start Function
[0] DC hold / delay time
[1] DC brake / delay time
*[2] Coast / delay time
1-73 Start Mode
*[0] Disabled
[1] Enable - Catch Spinning Load
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at Stop [Hz]
0.0 - 20.0 Hz * 0.0 Hz
1-9* Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Termistor warning
[2] Thermistor trip
[3] Electronic Overload warning
[4] Electronic Overload trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0* DC-Brake
2-00 DC Hold Current
0 - 150 % * 50 %
2-01 DC Brake Current
0 - 150 % * 50 %
2-02 DC Braking Time
0.0 - 60.0 s * 10.0 s
2-04 DC Brake Cut In Speed
0.0 - 400.0 Hz * 0.0 Hz
2-1* Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5 - 5000 * 5
2-16 AC Brake, Max current
0 - 150 % * 100 %
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00 - 100.0 A * 0.00 A
2-22 Activate Brake Speed [Hz]
0.0 - 400.0 Hz * 0.0 Hz
3-** Reference / Ramps
3-0* Reference Limits
3-00 Reference Range
*[0] Min - Max
[1] -Max - +Max
3-02 Minimum Reference
-4999 - 4999 * 0.000
3-03 Maximum Reference
-4999 - 4999 * 50.00
3-1* References
3-10 Preset Reference
-100.0 - 100.0 % * 0.00 %
3-11 Jog Speed [Hz]
0.0 - 400.0 Hz * 5.0 Hz
3-12 Catch up/slow Down Value
0.00 - 100.0 % * 0.00 %