5-55 Terminal 33 Low Frequency
Range: Function:
20 Hz
*
[20 - 4999 Hz]
Enter low frequency corresponding to low motor shaft speed (i.e. low reference value) in par. 5-57.
5-56 Terminal 33 High Frequency
Range: Function:
5000 Hz
*
[21 - 5000 Hz]
Enter high frequency corresponding to high motor shaft speed (i.e. high reference value) in par. 5-58.
5-57 Terminal 33 Low Ref./Feedb. Value
Range: Function:
0.000
*
[-4999 - 4999]
Set reference/feedback value corresponding to low pulse frequency value set in par. 5-55.
5-58 Terminal 33 High Ref./Feedb. Value
Range: Function:
50.000
*
[-4999 - 4999]
Set reference/feedback value corresponding to high pulse frequency value set in par. 5-56.