EasyManuals Logo

GE AKR-50 Installation Manual

GE AKR-50
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
GEI
-
86150
-
A
TRIPPING
In
the
closed
position
,
the
breaker
’
s
movable
contacts
are
held
in
by
a
toggle
linkage
.
The
breaker
is
tripped
open
by
displacing
a
mechanism
latch
which
allows
this
toggle
linkage
to
collapse
.
The
trip
latch
is
rigidly
fastened
to
a
horizontal
trip
shaft
running
from
left
to
right
through
the
breaker
.
In
turn
,
the
tripshaftcarries
paddles
actuated
by
the
manual
trip
button
and
the
various
other
trip
devices
—
overcurrent
,
reverse
current
,
shunt
trip
,
undervoltage
,
open
fuse
lockout
.
Viewing
the
breaker
from
the
right
,
rotating
the
trip
shaft
counterclockwise
trips
the
breaker
;
clockwise
movement
resets
the
mechanism
latch
.
In
addition
to
tripping
the
breaker
,
some
devices
hold
the
breaker
trip
free
,
i
.
e
.
,
prevent
the
contacts
from
closing
even
though
a
closing
impulse
is
applied
to
the
mechanism
.
Such
devices
are
the
undervoltage
,
bell
alarm
and
lockout
,
electric
lockout
,
open
fuse
lockout
,
and
the
key
operated
locks
.
These
devices
and
the
drawout
mechanism
interlocks
must
be
in
the
reset
position
before
the
breaker
can
be
closed
.
FUSED
BREAKERS
The
AKRU
-
30
/
50
type
breakers
employ
current
limiting
fused
mounted
integrally
with
the
breaker
(
see
Fig
.
9
)
.
Included
is
an
open
fuse
lockout
device
(
OFLO
)
to
'
prevent
single
-
phasing
in
the
event
only
one
fuse
blows
.
across
its
corresponding
fuse
.
The
arc
voltage
generated
by
a
blown
fuse
activates
its
OFLO
shunt
trip
coil
,
thereby
tripping
the
breaker
and
preventing
single
phase
power
from
being
supplied
to
the
load
.
An
indicator
on
the
OFLO
device
signals
which
fuse
is
blown
.
The
breaker
cannot
be
closed
until
the
blown
fuse
is
acknowledged
by
resetting
the
OFLO
.
The
fuse
,
of
course
,
must
be
replaced
.
The
OFLO
is
a
special
trip
device
having
three
(
3
)
shunt
trip
elements
(
one
per
phase
)
,
the
coil
of
each
being
connected
MAINTENANCE
INSPECTION
3
.
Visually
check
the
breaker
for
loose
hardware
on
the
breaker
and
the
bottom
of
the
compartment
for
any
hardware
that
has
fallen
from
the
breaker
.
4
.
Remove
the
arc
quenchers
and
inspect
the
arc
quenchers
and
contacts
for
breakage
or
excessive
burning
.
5
.
The
performance
of
the
solid
-
state
current
trip
devices
may
be
checked
with
a
suitable
test
set
.
Check
electrome
-
chanical
devices
for
positive
trip
in
accordance
with
the
instructions
in
their
Maintenance
Manual
.
(
GEK
-
64459
)
6
.
Check
insulating
parts
for
evidence
of
overheating
and
for
cracks
that
indicate
excessive
thermal
aging
.
Periodic
inspection
of
the
circuit
breaker
is
recommended
at
least
once
a
year
.
More
frequent
inspections
are
recom
-
mended
where
severe
load
conditions
,
dust
,
moisture
or
other
unfavorable
conditions
exist
,
or
if
the
vital
nature
of
the
load
warrants
it
.
Always
inspect
the
breaker
after
a
short
-
circuit
current
has
been
interrupted
.
At
the
time
of
inspection
,
the
following
checks
should
be
made
after
the
breaker
has
been
deenergized
:
1
.
Manually
operate
the
breaker
several
times
,
checking
for
obstructions
or
excessive
friction
.
Manual
closing
of
an
electri
-
cally
operated
breaker
may
be
performed
by
the
following
two
steps
:
(
1
)
Install
maintenance
crank
(
568
B
386
G
1
)
to
the
motor
gear
reducer
shaft
on
the
front
right
side
of
the
breaker
.
Ratchet
the
maintenance
crank
up
and
down
until
the
springs
are
fully
charged
as
indicated
by
the
distinct
click
as
the
prop
is
set
and
prevents
any
further
charging
of
the
closing
springs
.
After
the
prop
is
set
do
not
apply
undue
force
to
the
maintenance
handle
.
(
2
)
Manually
pull
the
armature
of
the
closing
solenoid
(
located
behind
the
lower
right
-
hand
corner
of
the
escutcheon
)
toward
the
front
of
the
breaker
.
This
dislodges
the
prop
and
allows
the
closing
springs
to
discharge
,
closing
the
breaker
.
2
.
Electrically
operate
the
breaker
several
times
to
check
performance
of
the
electrical
accessories
.
LUBRSCATSGN
In
general
,
the
circuit
breaker
requires
moderate
lubrication
.
Bearing
points
and
sliding
surfaces
should
be
lubricated
at
the
regular
inspection
periods
with
a
thin
film
of
GE
Lubricant
D
50
HD
38
(
Mobil
28
)
.
Before
lubricating
,
remove
any
hardened
grease
and
dirt
from
latch
and
bearing
surfaces
with
kerosene
.
ALL
EXCESS
LUBRICANT
SHOULD
BE
REMOVED
WITH
A
CLEAN
CLOTH
TO
AVOID
ACCUMULATION
OF
DIRT
OR
DUST
.
On
drawout
breakers
the
contact
surface
of
the
disconnect
studs
should
be
cleaned
and
greased
with
GE
Lubricant
D
50
HD
38
.
(
Order
part
number
193
A
1751
P
1
)
13
Courtesy of NationalSwitchgear.com

Other manuals for GE AKR-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AKR-50 and is the answer not in the manual?

GE AKR-50 Specifications

General IconGeneral
BrandGE
ModelAKR-50
CategoryCircuit breakers
LanguageEnglish

Related product manuals