9
Table 3 - Level II Programming Parameters
Parameter
Name Description Range of Values
Minimum
Increments
Default
Units of
Measure
Notes
P6 Refill controller 1 to 99 1 33
Enter the value molded into the
end of the refill controller.
P7
Regenerant
draw value
1 to 99 1 25
Select number from Table 4 and
enter that number.
P8 Not used NA NA NA NA NA
P9 Backwash time 3 to 30 1 14 Minutes
Skip this parameter to accept the
default or enter a value.
P10 Slow rinse time 8 to 125 1 40 Minutes
Skip this parameter to accept the
default or enter a value.
P11 Fast rinse time 2 to 19 1 4 Minutes
Skip this parameter to accept the
default or enter a value.
P12 Units of Measure 0 to 1 1 0
0 = U.S., 1 = metric. Skip this
parameter to accept U.S. or enter
1 for metric.
P13 Clock mode 0 to 1 1 0
0 = 12-hour clock.
1 = 24-hour clock. Skip this
parameter for a 12-hour clock or
enter 1 for a 24-hour clock.
P14
Calendar
override
0 to 30 1 0 Days
0 = no calendar override. Skip this
parameter for no calendar
override or enter a value.
P15 Reserve type 0 to 3 1 0
0 = variable reserve, 1 = fixed
reserve, 2 = variable reserve with
immediate regen,
3 = fixed reserve with immediate
regen. Skip this parameter to
accept the default or enter a
different reserve type.
P16
Fixed reserve
capacity or initial
average value
0 to 70 1 30
Percent of
capacity
Description depends on the value
entered for P15. Skip this
parameter to accept the default or
enter a different value.
P17 Operation type 0 to 2 1 2
2 = 5-cycle
cocurrent conditioner.
P18
Salt/capacity
change lockout
0 to 1 1 0
0 = none, 1 = salt/capacity change
locked out. Skip this parameter to
accept the default or enter 1 to
lock out salt/capacity change.
P19 Factory defaults 1 99
Loads in a set of default values.
Refer to the Special Notes for
Level II Parameters section in this
manual. Do Not Change.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Autotrol Performa ProSoft 960 Series and is the answer not in the manual?

GE Autotrol Performa ProSoft 960 Series Specifications

General IconGeneral
BrandGE
ModelAutotrol Performa ProSoft 960 Series
CategoryWater System
LanguageEnglish

Related product manuals