CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-193
3
3.5.6.7 Digital counters (DigCnt)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-210: Digital counter data objects
stVal BOOLEAN ST Transitions to true whenever a
new sample is recorded, cleared
to false when recorder is
cleared.
R
MemClr SPC Clear all data logger records command R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF DatLogRDRE1.MemClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
InRef1 ORG DATA LOGGER TRIGGER setting. R
setSrcRef ObjectReference SP DATA LOGGER TRIGGER setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DigCntFCNT# LDevice inst: Gen UR element: Digital Counters #
data obj. data attribute Type FC UR Name Description R/W/C
HiLim SPS Counter #(CNT#) HI, which indicates the
number of pulses counted is above the
set number.
R
stVal BOOLEAN ST Counter #(CNT#) HI R
EqLim SPS Counter #(CNT#) EQL operand, which
indicates the number of pulses counted is
equal to the set number
R
stVal BOOLEAN ST Counter #(CNT#) EQL R
LoLim SPS Counter #(CNT#) LO operand, which
indicates the number of pulses counted is
below the set number.
R
stVal BOOLEAN ST Counter #(CNT#) LO R
CntVal BCR Counter # ACCUM, which indicates the
accumulated number of pulses
R
actVal INT64 ST actual value of Counter #
ACCUM
R
frVal INT64 ST actual value of Counter #
FROZEN (count)
R
frTm TimeStamp ST actual value of Counter #
FROZEN (date/time) combined
with Counter # MICROS
(fractional seconds)
R
units.SIUnit ENUMERATED COUNTER # UNITS R
units.multiplier ENUMERATED COUNTER # UNITS R
pulsQty FLOAT32 CF 1 R
frEna BOOLEAN CF R
strTm TimeStamp CF 0 R
frPd INT32 CF 0 R
frRs BOOLEAN CF R
InRef1 ORG COUNTER # UP setting. R
setSrcRef ObjectReference SP COUNTER # UP setting reference to the data attribute to input R/C
LNName: DatLogRDRE1 LDevice inst: Gen UR element: Data Logger
data obj. data attribute Type FC UR Name Description R/W/C