EasyManua.ls Logo

GE b30 - Page 431

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-193
3
3.5.6.7 Digital counters (DigCnt)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-210: Digital counter data objects
stVal BOOLEAN ST Transitions to true whenever a
new sample is recorded, cleared
to false when recorder is
cleared.
R
MemClr SPC Clear all data logger records command R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF DatLogRDRE1.MemClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
InRef1 ORG DATA LOGGER TRIGGER setting. R
setSrcRef ObjectReference SP DATA LOGGER TRIGGER setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DigCntFCNT# LDevice inst: Gen UR element: Digital Counters #
data obj. data attribute Type FC UR Name Description R/W/C
HiLim SPS Counter #(CNT#) HI, which indicates the
number of pulses counted is above the
set number.
R
stVal BOOLEAN ST Counter #(CNT#) HI R
EqLim SPS Counter #(CNT#) EQL operand, which
indicates the number of pulses counted is
equal to the set number
R
stVal BOOLEAN ST Counter #(CNT#) EQL R
LoLim SPS Counter #(CNT#) LO operand, which
indicates the number of pulses counted is
below the set number.
R
stVal BOOLEAN ST Counter #(CNT#) LO R
CntVal BCR Counter # ACCUM, which indicates the
accumulated number of pulses
R
actVal INT64 ST actual value of Counter #
ACCUM
R
frVal INT64 ST actual value of Counter #
FROZEN (count)
R
frTm TimeStamp ST actual value of Counter #
FROZEN (date/time) combined
with Counter # MICROS
(fractional seconds)
R
units.SIUnit ENUMERATED COUNTER # UNITS R
units.multiplier ENUMERATED COUNTER # UNITS R
pulsQty FLOAT32 CF 1 R
frEna BOOLEAN CF R
strTm TimeStamp CF 0 R
frPd INT32 CF 0 R
frRs BOOLEAN CF R
InRef1 ORG COUNTER # UP setting. R
setSrcRef ObjectReference SP COUNTER # UP setting reference to the data attribute to input R/C
LNName: DatLogRDRE1 LDevice inst: Gen UR element: Data Logger