2-94 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 67D2 DUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67D3 DUTT RX1 0 to 4294967295 --- 1 F300 0
" 67D5 DUTT RX2 0 to 4294967295 --- 1 F300 0
" 67D7 DUTT RX3 0 to 4294967295 --- 1 F300 0
" 67D9 DUTT RX4 0 to 4294967295 --- 1 F300 0
" 67DB DUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67DC DUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67DD DUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67DF Reserved (6 items) 0 to 1 --- 1 F001 0
Pilot PUTT (1P) (Read/Write Setting)
D60, L90 67EA PUTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" 67EB PUTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 67EC PUTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 67ED PUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
" 67EE PUTT 1P Rx1 0 to 4294967295 --- 1 F300 0
" 67F0 PUTT 1P Rx2 0 to 4294967295 --- 1 F300 0
" 67F2 PUTT 1P Rx3 0 to 4294967295 --- 1 F300 0
" 67F4 PUTT 1P Rx4 0 to 4294967295 --- 1 F300 0
" 67F6 PUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 67F7 PUTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 67F8 PUTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
" 67FA Reserved (5 items) 0 to 1 --- 1 F001 0
Pilot Hybrid POTT (1P) (Read/Write Setting)
D60, L90 6820 Hybrid POTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" 6821 Hybrid POTT 1P Permissive Echo 0 to 2 --- 1 F199 0 (Disabled)
" 6822 Hybrid POTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" 6823 Hybrid POTT 1P Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 20
" 6824 Hybrid POTT 1P Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
" 6825 Hybrid POTT 1P Echo Duration 0 to 65.535 s 0.001 F001 100
" 6826 Hybrid POTT 1P Echo Lockout 0 to 65.535 s 0.001 F001 250
" 6827 Hybrid POTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 6828 Hybrid POTT 1P Ground Directional
Overcurrent Forward
0 to 4294967295 --- 1 F300 0
" 682A Hybrid POTT 1P Gnd Directional
Overcurrent Reverse
0 to 4294967295 --- 1 F300 0
" 682C Hybrid POTT 1P Number of Communication
Bits
0 to 2 --- 1 F198 0 (1)
" 682D Hybrid POTT 1P Rx1 0 to 4294967295 --- 1 F300 0
" 682F Hybrid POTT 1P Rx2 0 to 4294967295 --- 1 F300 0
" 6831 Hybrid POTT 1P Rx3 0 to 4294967295 --- 1 F300 0
" 6833 Hybrid POTT 1P Rx4 0 to 4294967295 --- 1 F300 0
" 6835 Hybrid POTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6836 Hybrid POTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
" 6837 Hybrid POTT 1P Echo Condition 0 to 4294967295 --- 1 F300 0
" 6839 Hybrid POTT 1P Weak Infeed 0 to 2 --- 1 F199 1 (Enabled)
" 683A Hybrid POTT 1P Weak Infeed Condition 0 to 4294967295 --- 1 F300 0
" 683C Hybrid POTT 1P Block 0 to 4294967295 --- 1 F300 0
" 683E Reserved (3 items) 0 to 1 --- 1 F001 0
Products Address Register name Range Units Step Format Default