2-116 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 789F ...Repeated for PMU 4
" 78A4 ...Repeated for PMU 5
" 78A9 ...Repeated for PMU 6
Phasor Measurement Unit Test Values (Read/Write Setting) (1, 2, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
78AE PMU 1 Test Function 0 to 1 --- 1 F102 0 (Disabled)
" 78AF PMU 1 Phase A Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
" 78B1 PMU 1 Page A Voltage Test Angle -180 to 180 ° 0.05 F002 0
" 78B2 PMU 1 Phase B Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
" 78B4 PMU 1 Phase B Voltage Test Angle -180 to 180 ° 0.05 F002 -12000
" 78B5 PMU 1 Phase C Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
" 78B7 PMU 1 Phase C Voltage Test Angle -180 to 180 ° 0.05 F002 12000
" 78B8 PMU 1 Auxiliary Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
" 78BA PMU 1 Auxiliary Voltage Test Angle -180 to 180 ° 0.05 F002 0
" 78BB PMU 1 Phase A Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
" 78BD PMU 1 Phase A Current Test Angle -180 to 180 ° 0.05 F002 -1000
" 78BE PMU 1 Phase B Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
" 78C0 PMU 1 Phase B Current Test Angle -180 to 180 ° 0.05 F002 -13000
" 78C1 PMU 1 Phase C Current Test Magnitude 0 to 9.999 kA 0.001 F003 1000
" 78C3 PMU 1 Phase C Current Test Angle -180 to 180 ° 0.05 F002 11000
" 78C4 PMU 1 Ground Current Test Magnitude 0 to 9.999 kA 0.001 F004 0
" 78C6 PMU 1 Ground Current Test Angle -180 to 180 ° 0.05 F002 0
" 78C7 PMU 1 Test Frequency 20 to 70 Hz 0.001 F003 60000
" 78C9 PMU 1 Test df/dt -10 to 10 Hz/s 0.01 F002 0
C60, N60 78CA ...Repeated for PMU 2
N60 78E6 ...Repeated for PMU 3
" 7902 ...Repeated for PMU 4
" 791E ...Repeated for PMU 5
" 793A ...Repeated for PMU 6
Validation Automation (Read/Write Setting)
All 7A00 Validation Automation Setting (16 items) 0 to 4294967295 --- 1 F003 0
Underfrequency (Read/Write Setting) (6 Modules)
D30, D60, F35,
F60, G30, G60,
L30, L90, M60,
N60, T35, T60
7A60 Underfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 7A61 Underfrequency 1 Block 0 to 4294967295 --- 1 F300 0
" 7A63 Underfrequency 1 Min Current 0.1 to 1.25 pu 0.01 F001 10
" 7A64 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 5950
" 7A65 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 2000
" 7A66 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 2000
" 7A67 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 7A68 Underfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 7A69 Underfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7A6A Underfrequency 1 Reserved (5 items) 0 to 1 --- 1 F001 0
" 7A6F ...Repeated for Underfrequency 2
" 7A7E ...Repeated for Underfrequency 3
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals