2-130 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 9015 ...Repeated for FlexElement 2
" 902A ...Repeated for FlexElement 3
" 903F ...Repeated for FlexElement 4
" 9054 ...Repeated for FlexElement 5
" 9069 ...Repeated for FlexElement 6
" 907E ...Repeated for FlexElement 7
" 9093 ...Repeated for FlexElement 8
C70, F35, G30,
G60, M60, N60,
T35, T60
90A8 ...Repeated for FlexElement 9
" 90BD ...Repeated for FlexElement 10
" 90D2 ...Repeated for FlexElement 11
" 90E7 ...Repeated for FlexElement 12
" 90FC ...Repeated for FlexElement 13
" 9111 ...Repeated for FlexElement 14
" 9126 ...Repeated for FlexElement 15
" 913B ...Repeated for FlexElement 16
Fault Report Settings (Read/Write Setting) (1, 2, 3, 4, or 5 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90
91F0 Fault Report 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 91F1 Fault Report 1 Trigger 0 to 4294967295 --- 1 F300 0
" 91F3 Fault Report 1 Z1 Magnitude 0.01 to 250 ohms 0.01 F001 300
" 91F4 Fault Report 1 Z1 Angle 25 to 90 degrees 1 F001 75
" 91F5 Fault Report 1 Z0 Magnitude 0.01 to 650 ohms 0.01 F001 900
" 91F6 Fault Report 1 Z0 Angle 25 to 90 degrees 1 F001 75
" 91F7 Fault Report 1 Line Length Units 0 to 1 --- 1 F147 0 (km)
" 91F8 Fault Report 1 Line Length 0 to 2000 --- 0.1 F001 1000
" 91F9 Fault Report 1 VT Substitution 0 to 2 --- 1 F270 0 (None)
" 91FA Fault Report 1 System Z0 Magnitude 0.01 to 650 ohms 0.01 F001 200
" 91FB Fault Report 1 System Z0 Angle 25 to 90 degrees 1 F001 75
" 91FC Fault REM1-TAP Z1 Magnitude 0.01 to 250 ohms 0.01 F001 300
" 91FD Fault REM1-TAP Z1 Angle 25 to 90 degrees 1 F001 75
" 91FE Fault REM1-TAP Length 0 to 2000 --- 0.1 F001 1000
" 91FF Fault REM2-TAP Z1 Magnitude 0.01 to 250 ohms 0.01 F001 300
" 9200 Fault REM2-TAP Z1 Angle 25 to 90 degrees 1 F001 75
" 9201 Fault REM2-TAP Length 0 to 2000 --- 0.1 F001 1000
C60, D60, F35,
F60, L30, L60,
L90
9202 ...Repeated for Fault Report 2
C60, D60, F35,
F60, L90
9214 ...Repeated for Fault Report 3
C60, F35, L90 9226 ...Repeated for Fault Report 4
F35 9238 ...Repeated for Fault Report 5
Fault Report Parallel Line Settings (Read/Write Setting) (1, 2, 3, 4 or 5 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90
924A Fault Z0M Magnitude 0 to 650 ohm 0.01 F001 0
" 924B Fault Z0M Angle 25 to 90 degrees 1 F001 75
Products Address Register name Range Units Step Format Default